Figure 9.13 Correct Method to Install Live Parts and Control Signals
9.6 24 V Backup Option MCB 107
An external 24 V DC supply can be installed for low-voltage supply to the control card and any installed options card,
enabling full operation of the LCP without connection to the line power.
External 24 V DC Supply Specification
Input voltage range
24 V DC
±
15% (max. 37 V in 10 s)
Max. input current
2.2 A
Average input current for FC 302
0.9 A
Max cable length
250 ft [75 m]
Input capacitance load
10 uF
Power-up delay
0.6 s
The inputs are protected.
Options and Accessories