Electrical Data
Relays
Numbers
4 SPDT
Load at 250 V AC/30 V DC
8A
Load at 250 V AC/30 V DC with cosφ =0.4
3.5 A
Overvoltage category (contact - ground)
III
Overvoltage category (contact - contact)
II
Combination of 250 V and 24 V signals
Possible with one unused relay in between
Maximum thru-put delay
10 ms
Isolated from ground/chassis for use on IT line power systems
Digital Inputs
Numbers
7
Range
0/24 V
Mode
PNP/NPN
Input impedance
4 kW
Low trigger level
6.4 V
High trigger level
17 V
Maximum through-put delay
10 ms
Analog Outputs
Numbers
2
Range
0/4–20 mA
Resolution
11 bit
Linearity
<0.2%
Analog Outputs
Numbers
2
Range
0/4–20 mA
Resolution
11 bit
Linearity
<0.2%
EMC
EMC
IEC 61000-6-2 and IEC 61800-3 regarding Immunity of BURST, ESD, SURGE and Conducted Immunity
Options and Accessories