525–690 V AC
FC 302 [T7]
Pm (HO) (hp [kW])
Number of brake choppers
(1)
R
min
R
br,nom
N55K
75 [55]
1
13.5
11.0
N75K
100 [75]
1
8.8
9.4
N90K
125 [90]
1
8.2
7.5
N110
150 [110]
1
6.6
6.2
N132
175 [132]
1
4.2
5.2
N160
225 [160]
1
4.2
4.2
N200
275 [200]
1
3.4
3.3
N250
350 [250]
1
2.3
2.8
N315
425 [315]
1
2.3
2.4
P355
475 [355]
1
2.3
2.4
P400
550 [400]
1
2.1
2.1
P500
650 [500]
1
2.0
2.0
P560
750 [560]
1
2.0
2.0
P630
850 [630]
2
1.3
1.3
P710
950 [710]
2
1.1
1.2
P800
1075 [800]
2
1.1
1.1
P900
1200 [900]
3
1.0
1.0
P1M0
1350 [1000]
3
0.8
0.84
P1M2
1600 [1200]
3
0.7
0.70
P1M4
1875 [1400]
4
0.55
0.60
Table 5.10 Brake Chopper Data 525–690 V
R
min
=Minimum brake resistance that can be used with this adjustable frequency drive. If the adjustable frequency drive includes multiple brake
choppers, the resistance value is the sum of all resisters in parallel.
R
br,nom
=Nominal resistance required to achieve 150% braking torque.
R
rec
=Resistance value of the recommended Danfoss brake resistor.
1)
Larger adjustable frequency drives include multiple inverter modules with a brake chopper in each inverter. Equal resistors should be connected
to each brake chopper.
How to Order
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.