Type designation
PK75
P1K1
P1K5
P2K2
Efficiency
(5)
0.97
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
3
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
4
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
5
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
Table 36: Mains Supply 3x525–600 V AC, P3K0–P7K5
Type designation
P3K0
P4K0
P5K5
P7K5
High/normal overload
(1)
HO NO HO NO HO
NO
HO
NO
Typical shaft output [kW]
3.0
4.0
5.5
7.5
Typical shaft output [hp]
4.0
5.0
7.5
10
Protection rating IP20/Chassis
Protection rating IP21/Type 1
A2
A2
A3
A3
IP55/Type 12
A5
A5
A5
A5
Output current
Continuous (3x525–550 V) [A]
5.2
6.4
9.5
11.5
Intermittent (3x525–550 V) [A]
7.8 5.7 9.6 7.0 14.3 10.5 17.3 12.7
Continuous (3x551–600 V) [A]
4.9
6.1
9.0
11
Intermittent (3x551–600 V) [A]
7.4 5.4 9.2 6.7 13.5 9.9
16.5 12.1
Continuous kVA at 550 V [kVA]
5.0
6.1
9.0
11
Continuous kVA at 550 V [kVA]
4.9
6.1
9.0
11
Maximum input current
Continuous (3x525–600 V) [A]
5.2
5.8
8.6
10.4
Intermittent (3x525–600 V) [A]
7.8 5.7 8.7 6.4 12.9 9.5
15.6 11.4
Maximum pre-fuses [A]
20
20
32
32
Additional specifications
Maximum cable cross-section
(2)
for mains, motor, brake, and load sharing
[mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
Maximum cable cross-section
(2)
for mains disconnect [mm
2
(AWG)]
6, 4, 4 (10, 12, 12)
Estimated power loss
(3)
at rated maximum load [W]
(4)
122
145
195
261
AJ300847815559en-000101 / 130R0337 | 83
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide