N O T I C E
The measurements in the following tables are carried out with a single power size and motor, but with several motor cable
lengths, are for information only. Depending on the combination of drive, motor cable type, motor cable length, and motor, the
values for Upeak and dU/dt can be higher at the motor terminal. Sometimes, the values exceed the limits given by the motor
manufacturer.
To avoid problems with too high dU/dt, use motor cables longer than 30–40 m (98–131 ft).
If in doubt, use a dU/dt filter between the drive and the motor, or do a measurement in the actual installation.
10.15 Electromagnetic Compatibility (EMC) Overview
10.15.1 EMC Test Results
The following test results have been obtained by using a system with a drive, a shielded control cable, a control box with potentiom-
eter, a single motor, and shielded motor cable (Ölflex Classic 100 CY) at nominal switching frequency. See
for the maximum
motor cable lengths for compliance.
N O T I C E
Conditions may change significantly for other setups.
N O T I C E
for parallel motor cables.
Table 91: EMC Test Results (Emission) Maximum Motor Cable Length
RFI filter type
Conducted emission
Radiated emission
Cable length [m (ft)]
Standards
and require-
ments
EN 55011/CISPR 11
Class B
Class A, Group
1
Class A, Group
2
Class B
Class A,
Group 1
Class A,
Group 2
EN/IEC 61800-3
Category
C1
Category C2
Category C3
Catego-
ry C1
Category
C2
Category
C3
H1
FC 202
0.25–45 kW, 200–
240 V
T2 50 (164)
150 (492)
150 (492)
No
Yes
Yes
1.1–7.5 kW, 200–
240 V
S2 50 (164)
100/150
(164/492)
(1)
100/150
(164/492)
(1)
No
Yes
Yes
0.37–90 kW, 380–
480 V
T4 50 (164)
150 (492)
150 (492)
No
Yes
Yes
7.5 kW, 380–480 V S4 50 (164)
100/150
(164/492)
(1)
100/150
(164/492)
(1)
No
Yes
Yes
H2
FC 202
0.25–3.7 kW, 200–
240 V
T2 No
No
5 (16.4)
No
No
Yes
5.5–45 kW, 200–
240 V
T2 No
No
25 (82)
No
No
Yes
1.1–7.5 kW, 200–
240 V
S2 No
No
25 (82)
No
No
Yes
AJ300847815559en-000101 / 130R0337
146 | Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide