Type designation
P11K
P15K
P18K
P22K
P30K
Continuous kVA at 400 V [kVA]
11
16.6 16.6 22.2 22.2 26
26
30.5 30.5 42.3
Continuous kVA at 460 V [kVA]
11.6 16.7 16.7 21.5 21.5 27.1 27.1 31.9 31.9 41.4
Maximum input current
Continuous (3x380–440 V) [A]
14.4 22
22
29
29
34
34
40
40
55
Intermittent (60 s overload) (3x380–440 V) [A]
23
24.2 35.2 31.9 46.4 37.4 54.4 44
64
60.5
Continuous (3x441–480 V) [A]
13
19
19
25
25
31
31
36
36
47
Intermittent (60 s overload) (3x441–480 V) [A]
20.8 20.9 30.4 27.5 40
34.1 49.6 39.6 57.6 51.7
Maximum pre-fuses [A]
63
63
63
63
80
Additional specifications
Protection ratings IP21, IP55, IP66 maximum cable cross-sec-
tion
(3)
for mains, brake, and load sharing [mm
2
(AWG)]
16, 10, 16 (6, 8, 6)
35, -, - (2, -, -)
Protection ratings IP21, IP55, IP66 maximum cable cross-sec-
tion
(3)
for motor [mm
2
(AWG)]
10, 10, – (8, 8, –)
35, 25, 25 (2, 4, 4)
Protection rating IP20 maximum cable cross-section
(3)
for
mains, brake, motor, and load sharing [mm
2
(AWG)]
10, 10, – (8, 8, –)
35, –, – (2, –, –)
Maximum cable cross-section
(3)
for disconnect [mm
2
(AWG)]
16, 10, 10 (6, 8, 8)
Estimated power loss
(4)
at rated maximum load [W]
(5)
225
278
291
392
379
465
444
525
547
698
Efficiency
(6)
0.98
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Enclosure sizes B3+B4 and C3+C4 can be converted to IP21 using a conversion kit. See also chapters Mechanical mounting and IP21/Type 1 Enclo-
sure kit in the design guide.
3
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
.
5
Efficiency measure at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
. For efficiency class see
.
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
. For efficiency class see
.
Table 34: Mains Supply 3x380–480 V AC, P37K–P90K
Type designation
P37K
P45K
P55K
P75K
P90K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output [kW]
30
37
37
45
45
55
55
75
75
90
Typical shaft output at 460 V [hp]
40
50
50
60
60
75
75
100
100
125
Protection rating IP20/Chassis
(2)
B4
C3
C3
C4
C4
Protection rating IP21/Type 1
C1
C1
C1
C2
C2
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
C1
C1
C1
C2
C2
AJ300847815559en-000101 / 130R0337
80 | Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide