
Type designation
P5K5
P7K5
P11K
P15K
Estimated power loss
(4)
at rated maximum load
[W]
(5)
239
310
239
310
371
514
463
602
Efficiency
(6)
0.96
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Enclosure sizes B3+B4 and C3+C4 can be converted to IP21 using a conversion kit. See also chapters Mechanical mounting and IP21/Type 1 Enclo-
sure kit in the design guide.
3
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
5
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
Table 29: Mains Supply 3x200–240 V AC, P18K–P45K
Type designation
P18K
P22K
P30K
P37K
P45K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output [kW]
15
18.5 18.5 22
22
30
30
37
37
45
Typical shaft output at 208 V [hp]
20
25
25
30
30
40
40
50
50
60
Protection rating IP20/Chassis
(2)
B4
C3
C3
C4
C4
Protection rating IP21/Type 1
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
C1
C1
C1
C2
C2
Output current
Continuous (3x200–240 V) [A]
59.4 74.8 74.8 88
88
115
115
143
143
170
Intermittent (3x200–240 V) [A]
89.1 82.3 112
96.8 132
127
173
157
215
187
Continuous kVA at 208 V [kVA]
21.4 26.9 26.9 31.7 31.7 41.4
41.4
51.5
51.5
61.2
Maximum input current
Continuous (3x200–240 V) [A]
54
68
68
80
80
104
104
130
130
154
Intermittent (3x200–240 V) [A]
81
74.8 102
88
120
114
156
143
195
169
Maximum pre-fuses [A]
125
125
160
200
250
Additional specifications
Protection rating IP20 maximum
cable cross-section for mains,
brake, motor, and load sharing
[mm
2
(AWG)]
35 (2)
50 (1)
50 (1)
150 (300 MCM)
150 (300 MCM)
Protection ratings IP21, IP55, IP66
maximum cable cross-section for
mains and motor [mm
2
(AWG)]
50 (1)
50 (1)
50 (1)
150 (300 MCM)
150 (300 MCM)
AJ300847815559en-000101 / 130R0337 | 75
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide