Type designation
PK25
PK37
PK55
PK75
Efficiency
(6)
0.94
0.95
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Enclosure sizes A2+A3 can be converted to IP21 using a conversion kit. See also chapters Mechanical mounting and IP21/Type 1 Enclosure kit in the
design guide.
3
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
5
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
6
Measured using 5 m (16 ft) shielded motor c6ables at rated load and rated frequency. For more detailed efficiency values and part load losses
according IEC/EN 61800-9-2 refer to mydrive ecosmart on
Table 27: Mains Supply 3x200–240 V AC, P1K1–P3K7
Type designation
P1K1
P1K5
P2K2
P3K0
P3K7
High/normal overload
(1)
HO NO HO
NO HO
NO
HO
NO
HO
NO
Typical shaft output [kW]
1.1
1.5
2.2
3.0
3.7
Typical shaft output at 208 V [hp]
1.5
2.0
3.0
4.0
5.0
Protection rating IP20/Chassis
(2)
A2
A2
A2
A3
A3
Protection rating IP21/Type 1
A2
A2
A2
A3
A3
Protection rating IP55/Type 12
A4/A5
A4/A5
A4/A5
A5
A5
Protection rating IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous (3x200–240 V) [A]
6.6
7.5
10.6
12.5
16.7
Intermittent (3x200–240 V) [A]
9.9 7.3 11.3 8.3 15.9 11.7 18.8 13.8 25
18.4
Continuous kVA at 208 V [kVA]
2.38
2.70
3.82
4.50
6.00
Maximum input current
Continuous (3x200–240 V) [A]
5.9
6.8
9.5
11.3
15
Intermittent (3x200–240 V) [A]
8.9 6.5 10.2 7.5 14.3 10.5 17
12.4 22.5 16.5
Maximum pre-fuses [A]
20
20
20
32
32
Additional specifications
Maximum cable cross-section
(3)
for mains, motor, brake, and
load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
minimum 0.2 (24))
Maximum cable cross-section
(3)
for mains disconnect [mm
2
(AWG)]
6, 4, 4 (10, 12, 12)
Estimated power loss
(4)
at rated maximum load [W]
(5)
63
82
116
155
185
AJ300847815559en-000101 / 130R0337 | 73
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide