Function:
Parameter 007
LCP copy
is used if you want to use the
LCP 2 control panel's integral copy function. The func-
tion is used if you want to copy all parameter setups
from one frequency converter to another by moving the
LCP 2 control panel.
Description of choice:
Select
Upload all parameters
[1] if you want all param-
eter values to be transferred to the control panel. Se-
lect
Download all parameters
[2] if all parameter values
transferred are to be copied to the frequency converter
to which the control panel is attached. Select
Down-
load size-independent par.
[3] if you only want to down-
loade the size-independent parameters. This is used
when downloading to a frequency converter with a dif-
ferent rated power size than that from which the pa-
rameter setup originates.
NB!
Upload/download can only be performed
in stop mode. Download can only be per-
formed to a frequency converter with the
same software version number, see pa-
rameter 626
Database identification no.
008
Display scaling of output frequency
(FREQUENCY SCALE)
Value:
0.01 - 100.00
1.00
Function:
In this parameter, the factor is selected by which the
output frequency is to be multiplied. The value is
shown in the display, provided parameters 009-012
Display readout
have been set to
Output frequency x
scaling
[5].
Description of choice:
Set the required scaling factor.
009
Large display readout
(DISPLAY LINE 2)
Value:
No readout (none)
[0]
Resulting reference [%]
(reference [%])
[1]
Resulting reference [unit]
(reference [unit])
[2]
Feedback [unit] (feedback [unit])
[3]
Frequency [Hz] (Frequency [Hz])
[4]
Output frequency x scaling
(frequency x scale)
[5]
Motor current [A] (Motor current [A])
[6]
Torque [%] (Torque [%])
[7]
Power [kW] (Power [kW])
[8]
Power [HP] (Power [HP][US])
[9]
Motor voltage [V]
(Motor voltage [V])
[11]
DC link voltage [V]
(DC link voltage [V])
[12]
Thermal load motor [%]
(Motor thermal [%])
[13]
Thermal load [%]
(FC. thermal[%])
[14]
Running hours [Hours]
(RUNNING HOURS])
[15]
Digital input [Bin]
(Digital input[bin])
[16]
Analog input 53 [V]
(analog input 53 [V])
[17]
Analog input 60 [mA]
(analog input 60 [mA])
[19]
Pulse reference [Hz]
(Pulse ref. [Hz])
[20]
External reference [%]
(external ref. [%])
[21]
Status word [Hex] (Status word [hex])
[22]
Heatsink temperature [°C]
(Heatsink temp [°C])
[25]
Alarm word [Hex] (Alarm word [hex])
[26]
Control word [Hex] (Control word [Hex])
[27]
Warning word [Hex]
(warning word [Hex])
[28]
Extended status word [Hex]
(Ext. status [hex])
[29]
Communication option card warning
(COMM OPT WARN [HEX])
[30]
Pulse count
(PULSE COUNTER)
[31]
Function:
In this parameter you can select the data value that
you wish to display in the LCP 2 control unit display
line 2 when the frequency converter is switched on.
The display will also be included in the scrollbar in dis-
play mode. In parameters 010-012
Display readout
you
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
12
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......