Quick Setup
General warning
Using this Quick Setup, you can carry out quick and
EMC-correct installation of the frequency converter in
five steps. The Operating Instructions, which are also
enclosed, give other examples of installation and de-
scribe all functions in detail.
Read the safety instructions on this page
before installing the unit.
Mechanical Installation
VLT 2800 frequency converters allow side-by-side in-
stallation. Because of the need for cooling, there must
be 10 cm free air passage above and below the fre-
quency converter. Drill holes in accordance with the
measurements given in section
Mechanical dimen-
stions
. Retighten all four screws.
Fit the decoupling plate to the power cables and the
earth screw (terminal 95).
Electrical Installation, power
Please note that the power terminals can be removed.
Connect mains to the mains terminals of the frequency
converter, i.e. 91, 92, 93 and the earth connection to
terminal 95. Fit a screened/armoured cable from the
motor to the motor terminals of the frequency convert-
er, i.e. U, V, W. The screen ends in a screen connector.
Electrical Installation, control cables
Remove the front cover underneath the control panel.
Place a jumper between terminals 12 and 27.
Programming
Carry out programming on the control panel. Press the
[QUICK MENU] key to enter the Quick menu. In this
menu, parameters can be selected by means of the [+]
and [-] keys. The parameter values can be changed by
pressing [CHANGE DATA]. Changes are programmed
using the [+] and [-] keys. Finish the change of a pa-
rameter setting by pressing [CHANGE DATA]. A
change of parameter values is saved automatically af-
ter a mains failure. If the display shows three dots at
the right, the parameter value has more than three
digits. In order to see the value, activate [CHANGE
DATA]. Press [QUICK MENU]: Set the motor param-
eters that are on the nameplate of the motor:
Motor power [kW]
parameter 102
Motor voltage [V]
parameter 103
Motor frequency [Hz]
parameter 104
Motor current [A]
parameter 105
Rated motor speed
parameter 106
Activate AMT:
Automatic motor tuning
parameter 107
Set reference range
Min. reference, RefMIN
parameter 204
Max. reference, RefMAX parameter 205
Ramp-up time [s]
parameter 207
Ramp-down time [s]
parameter 208
In parameter 002 Local/remote control, the frequency
converter mode can be selected as Remote operation
[0], i.e. via the control terminals, or Local [1], i.e. via
the control unit.
VLT
®
2800 Series
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
3
Qu
ic
k Setu
p
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......