Motor thermal protection
The electronic thermal relay in UL-approved frequency
converters has received the UL-approval for single
motor protection, when parameter 128
Motor thermal
protection
has been set for
ETR Trip
and parameter
105
Motor current, I
M, N
has been programmed to the
rated motor current (see motor nameplate).
Brake connection
No. 81
82 Brake resistor
R- R+ terminals
The connection cable to the brake resistor must be
screened/armoured. Connect the screen to the metal
cabinet of the frequency converter and to the metal
cabinet of the brake resistor by means of cable clamps.
Dimension the cross-section of the brake cable to
match the brake torque.
See the
Design Guide
for dimensioning of brake resis-
tors.
NB!
Please note that voltages up to 850 V DC
occur on the terminals.
Earth connection
As leak current to the earth is higher than 3.5 mA, the
frequency converter must always be earthed accord-
ing to prevailing national and local regulations. To
guarantee that the earth cable has a good mechanical
connection to terminal 95, the cable cross section must
be at least 10 mm
2
or 2 rated earth wires that are ter-
minated separately. To increase safety you can install
an RCD (Residual Current Device), which guarantees
that the frequency converter trips when leak current
becomes too high. See also RCD Application Note
MN.90.GX.02.
VLT
®
2800 Series
70
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......