Display readout states
Display mode
In normal operation, one item of operating data can be
displayed continuously at the operator's own choice.
By means of the [+/-] keys the following options can be
selected in Display mode:
-
Output frequency [Hz]
-
Output current [A]
-
Output voltage [V]
-
Intermediate circuit voltage [V]
-
Output power [kW]
-
Scaled output frequency f
out
x p008
Menu mode
In order to enter the Menu mode [QUICK MENU] + [+]
must be activated at the same time.
In Menu mode, most of the frequency converter pa-
rameters can be changed. Scroll through the param-
eters using the [+/-] keys. While scrolling in the Menu
mode proceeds, the parameter number will flash.
The display shows that the setting in parameter 102
Motor power P
M,N
is 0.75. In order to change the value
of 0.75, [CHANGE DATA] must first be activated; the
parameter value can then be changed using the [+/-]
keys.
If for a given parameter the display shows three dots
at the right, it means that the parameter value has
more than three digits. In order to see the value, acti-
vate [CHANGE DATA].
The display shows that in parameter 128
Motor thermal
protection
the selection made is
Thermistor trip
[2].
Quick menu
Using the [QUICK MENU] key, it is possible to access
the 12 most important parameters of the frequency
converter. After programming, the frequency converter
is in most cases ready for operation. When the [QUICK
MENU] key is activated in Display mode, the Quick
menu starts. Scroll through the quick menu using the
[+/-] keys and change the data values by first pressing
[CHANGE DATA] and then changing the parameter
value with the [+/-] keys.
TheQuick menu parameters are:
•
Par. 100
Configuration
•
Par. 101
Torque characteristic
•
Par. 102
Motor power P
M,N
•
Par. 103
Motor voltage U
M,N
•
Par. 104
Motor frequency f
M,N
•
Par. 105
Motor current I
M,N
•
Par. 106
Rated motor speed n
M,N
•
Par. 107
Automatic motor adaptation
•
Par. 202
Output frequency high limit f
MAX
•
Par. 203
Reference range
•
Par. 204
Minimum reference Ref
MIN
•
Par. 205
Maximum reference Ref
MAX
•
Par. 207
Ramp-up time
•
Par. 208
Ramp-down time
•
Par. 002
Local/remote operation
•
Par. 003
Local reference
Parameter 102 - 106 can be read out from the motor's
nameplate.
Hand Auto
During normal operation the frequency converter is in
Auto mode, where the reference signal is given exter-
nally, analog or digital via the control terminals. How-
ever, in Hand mode, it is possible to give the reference
signal locally via the control panel.
On the control terminals, the following control signals
will remain active when Hand mode is activated:
•
Hand Start (LCP2)
•
Off Stop (LCP2)
•
Auto Start (LCP2)
VLT
®
2800 Series
8
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......