Tightening torques, control cables
Control wires must be connected with a tightening tor-
que of 0.22-0.25 Nm.
Electrical installation, control terminals
See section entitled
Earthing of screened/armoured
control cables
in the VLT 2800 Design Guide for the
correct termination of control cables.
No.
Function
01-03
Relay outputs 01-03 can be used for
indicating status and alarms/warnings.
12
24 V DC voltage supply.
18-33
Digital inputs.
20, 55
Common frame for input
and output terminals.
42
Analog output for displaying frequency,
reference, current or torque.
46
1
Digital output for displaying status,
warnings or alarms, as well as
frequency output.
50
+10 V DC supply
voltage for potentiometer or thermistor.
53
Analogue voltage input 0 - 10 V DC.
60
Analogue current input 0/4 - 20 mA.
67
1
+ 5 V DC supply voltage
to Profibus.
68, 69
1
RS 485, Serial communication.
70
1
Frame for terminals 67, 68 and 69.
Normally this terminal is not to be used.
1. The terminals are not valid for DeviceNet/CANopen.
See also the DeviceNet manual, MG.90.BX.YY for fur-
ther details.
Relay connection
See parameter 323
Relay output
for programming of
relay output.
Nr.
01 - 02
1 - 2 make (normally open)
01 - 03
1 - 3 break (normally closed)
NB!
Please note that the cable jacket for the
relay must cover the first row of control
card terminals - otherwise the galvanic
isolation (PELV) cannot be maintained.
Max. cable diameter: 4 mm. See drawing.
Switches 1-4
The dip switch is only on the control card with Profibus
DP communication.
The switch position shown is the factory setting.
Switches 1 and 2 are used as cable termination for the
RS 485 interface. If the frequency converter is located
as the first or last unit in the bus SYSTEM, switches 1
and 2 must be ON. On the remaining frequency con-
verters, switches 1 and 2 must be OFF.
Switches 3 and 4 are not applied.
VLT Software Dialog
Connection to terminals 68-70 or
Sub D:
-
PIN 3 GND
-
PIN 8 P-RS 485
-
PIN 9 N-RS 485
Sub D plug
An LCP 2 control unit can be connected to the Sub D
plug on the control card. Ordering number: 175N0131.
LCP control unit with ordering number 175Z0401 is not
to be connected.
VLT
®
2800 Series
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
73
Installation
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......