References & Limits
200
Output frequency range
(OUT FREQ. RNG/ROT)
Value:
Only clockwise, 0 - 132 Hz
(132 Hz CLOCKWISE)
[0]
Both directions, 0 - 132 Hz
(132 Hz BOTH DIRECT)
[1]
Anti-clockwise only, 0 - 132 Hz
(132 Hz COUNTER CLOCK)
[2]
Clockwise only, 0 - 1000 Hz
(1000 Hz CLOCK WISE)
[3]
Both directions, 0 - 1000 Hz
(1000 Hz BOTH DIRECT)
[4]
Anti-clockwise only, 0 - 1000 Hz
(1000 Hz COUNTER CLOCK)
[5]
Function:
This parameter guarantees protection against unwan-
ted reversing. Furthermore, the maximum output fre-
quency can be selected that is to apply regardless of
the settings of other parameters. This parameter has
no function if
Process regulation, closed loop
has been
selected in parameter 100
Configuration
.
Description of choice:
Select the required direction of rotation as well as the
maximum output frequency. Please note that if
Clock-
wise only
[0]/[3] or
Anti-clockwise only
[2]/[5] is selec-
ted, the output frequency will be limited to the range
f
MIN
-f
MAX
. If
Both directions
[1]/[4] is selected, the out-
put frequency will be limited to the range ± f
MAX
(the
minimum frequency is of no significance).
201
Output frequency low limit, f
MIN
(MIN OUTPUT FREQ)
Value:
0.0 - f
MAX
0.0 Hz
Function:
In this parameter, a minimum motor frequency limit
can be selected that corresponds to the minimum
speed at which the motor is allowed to run. If
Both di-
rections
has been selected in parameter 200
Output
frequency range
, the minimum frequency is of no sig-
nificance.
Description of choice:
The value chosen can range from 0.0 Hz to the fre-
quency set in parameter 202
Output frequency high
limit, f
MAX
.
202
Output frequency high limit, f
MAX
(max. output freq)
Value:
f
MIN
- 132/1000 Hz (par. 200
Output fre-
quency range
)
132 Hz
Function:
In this parameter, a maximum output frequency limit
can be selected that corresponds to the highest speed
at which the motor is allowed to run.
NB!
The output frequency of the frequency
converter can never assume a value high-
er than 1/10 of the switching frequency
(parameter 411
Switching frequency
).
Description of choice:
A value can be selected from f
MIN
to the value chosen
in parameter 200
Output frequency range
.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
28
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......