004
Active Setup
(active Setup)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (setup 1)
[1]
Setup 2 (setup 2)
[2]
Setup 3 (setup 3)
[3]
Setup 4 (setup 4)
[4]
Multi Setup (MULTI SETUP)
[5]
Function:
The active parameter Setup is selected here. All pa-
rameters can be programmed in four individual pa-
rameter Setups. Shifts between Setups can be made
in this parameter via a digital input or via serial com-
munication.
Description of choice:
Factory Setup
[0] contains the factory-set parameter
values.
Setup 1-4
[1]-[4] are four individual Setups
which can be selected as required.
Multi Setup
[5] is
used where remote-controlled shifts between the four
Setups via a digital input or via serial communication
is required.
005
Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (setup 1)
[1]
Setup 2 (setup 2)
[2]
Setup 3 (setup 3)
[3]
Setup 4 (setup 4)
[4]
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control panel
and the serial communication port). It is, for example,
possible to programme
Setup 2
[2], while the active
Setup is set to
Setup 1
[1] in parameter 004
Active
Setup
.
Description of choice:
Factory Setup
[0] contains the factory-set data and can
be used as a source of data if the other Setups are to
be reset to a known status.
Setup 1-4
[1]-[4] are indi-
vidual Setups that can be programmed freely during
operation. If
Active Setup
[5] is selected, the program-
ming Setup will be equal to parameter 004
Active
Setup
.
NB!
If data is modified or copied to the active
Setup, the modifications have an immedi-
ate effect on the unit's operation.
006
Setup copying
(SETUP COPY)
Value:
No copying (NO COPY)
[0]
Copy to Setup 1 from #
(COPY TO SETUP 1)
[1]
Copy to Setup 2 from #
(COPY TO SETUP 2)
[2]
Copy to Setup 3 from #
(COPY TO SETUP 3)
[3]
Copy to Setup 4 from #
(COPY TO SETUP 4)
[4]
Copy to all Setups from # (copy to all)
[5]
Function:
You can copy from the selected active Setup in pa-
rameter 005
Programming setup
to the selected Setup
or Setups in this parameter.
NB!
Copying is only possible in Stop (motor
stopped in connection with a stop com-
mand).
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA] key
has been pushed. The display indicates when copying
is in progress.
007
LCP copy
(LCP COPY)
Value:
No copying (NO COPY)
[0]
Upload all parameters (UPL. ALL PAR.)
[1]
Download all parameters (DWNL. ALL PAR.)
[2]
Download size-independent parameters
(DWNL.OUTPIND.PAR.)
[3]
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
11
Programming
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......