Control unit
On the front of the frequency converter there is a con-
trol panel.
The control panel is divided into four function groups:
1.
Six-digit LED display.
2.
Keys for changing parameters and shifting
display function.
3.
Indicator lamps.
4.
Keys for local operation.
All displays of data are in the form of a six-digit LED
display capable of showing one item of operating data
continuously during normal operation. As a supple-
ment to the display, there are three indicator lamps for
indication of mains connection (ON), warning (WARN-
ING) and alarm (ALARM). Most of the frequency con-
verter's parameter Setups can be changed immedi-
ately via the control panel, unless this function has
been programmed as
Locked
[1] via parameter 018
Lock for data changes
.
Control keys
[QUICK MENU]
allows access to the parameters used
for the Quick menu.
The[QUICK MENU] key is also used if a change to a
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
[CHANGE DATA]
is used for changing a setting.
The [CHANGE DATA] key is also used for confirming
a change of parameter settings.
[+] / [-]
are used for selecting parameters and for
changing parameter values.
These keys are also used in Display mode for selecting
the display of an operating value.
The
[QUICK MENU] + [+]
keys must be pressed at the
same time to give access to all parameters. See
Menu
mode.
[STOP/RESET]
is used for stopping the connected
motor or for resetting the frequency converter after a
trip.
Can be selected as
Active
[1] or
Not active
[0] via pa-
rameter 014
Local stop/reset
. In Display mode, the
display will flash if the stop function is activated.
NB!
If the [STOP/RESET] key is set at
Not ac-
tive
[0] in parameter 014
Local stop/re-
set,
and there is no stop command via the
digital inputs or serial communication, the
motor can only be stopped by disconnect-
ing the mains voltage to the frequency
converter.
[START]
is used for starting the frequency converter.
It is always active, but the [START] key cannot over-
ride a stop command.
Manual initialisation
Disconnect mains voltage. Hold the [QUICK MENU] +
[+] + [CHANGE DATA] keys down while simultane-
ously reconnecting the mains voltage. Release the
keys; the frequency converter has now been program-
med for the factory setting.
VLT
®
2800 Series
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
7
Introduc
tion to VLT 2800
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......