5 Specifications
5.1 Relays
Number
4 SPDT
Load at 250 V AC/30 V DC
8 A
Load at 250 V AC/30 V DC with cos φ = 0.4
3.5 A
Overvoltage category (contact-ground)
III
Overvoltage category (contact-contact)
II
Combination of 250 V and 24 V signals
Possible with 1 unused relay in between
5.2 Digital Inputs
Number
7
Range
0/24 V
Mode
PNP/NPN
Input impedance
4 kΩ
Low trigger level
6.4 V
High trigger level
17 V
5.3 Analog Outputs
Number
2
Range
0/4–20 mA
Resolution
11 bit
Linearity
<0.2%
5.4 EMC
EMC
IEC 61000-6-2 and IEC 61800-3 regarding Immunity of BURST, ESD, SURGE and Conducted Immunity
Specifications
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
50 | Danfoss A/S © 2020.01
Summary of Contents for MCB 113
Page 2: ......