Option
Function
[46]
Bus ctrl, 1 if time-
out
Controls the output via bus. The state of the output is set in
parameter 5-90 Digital & Relay Bus Control
.
If a bus timeout occurs, the output state is set high (on).
[47]
Bus ctrl, 0 if time-
out
Controls the output via bus. The state of the output is set in
parameter 5-90 Digital & Relay Bus Control
.
If a bus timeout occurs, the output state is set low (off).
[51]
MCO controlled
Active when an VLT® Advanced Cascade Controller MCO 102 or VLT® Motion Control MCO 305 is con-
nected. The output is controlled from the option.
[60]
Comparator 0
See
parameter group 13-1* Comparators
. If comparator 0 in SLC is true, the output goes high. Other-
wise, it is low.
[61]
Comparator 1
See
parameter group 13-1* Comparators
. If comparator 1 in SLC is true, the output goes high. Other-
wise, it is low.
[62]
Comparator 2
See
parameter group 13-1* Comparators
. If comparator 2 in SLC is true, the output goes high. Other-
wise, it is low.
[63]
Comparator 3
See
parameter group 13-1* Comparators
. If comparator 3 in SLC is true, the output goes high. Other-
wise, it is low.
[64]
Comparator 4
See
parameter group 13-1* Comparators
. If comparator 4 in SLC is true, the output goes high. Other-
wise, it is low.
[65]
Comparator 5
See
parameter group 13-1* Comparators
. If comparator 5 in SLC is true, the output goes high. Other-
wise, it is low.
[70]
Logic rule 0
See
parameter group 13-4* Smart Logic Control
. If logic rule 0 in SLC is true, the output goes high. Oth-
erwise, it is low.
[71]
Logic rule 1
See
parameter group 13-4* Smart Logic Control
. If logic rule 1 in SLC is true, the output goes high. Oth-
erwise, it is low.
[72]
Logic rule 2
See
parameter group 13-4* Smart Logic Control
. If logic rule 2 in SLC is true, the output goes high. Oth-
erwise, it is low.
[73]
Logic rule 3
See
parameter group 13-4* Smart Logic Control
. If logic rule 3 in SLC is true, the output goes high. Oth-
erwise, it is low.
[74]
Logic rule 4
See
parameter group 13-4* Smart Logic Control
. If logic rule 4 in SLC is true, the output goes high. Oth-
erwise, it is low.
[75]
Logic rule 5
See
parameter group 13-4* Smart Logic Control
. If logic rule 5 in SLC is true, the output goes high. Oth-
erwise, it is low.
[80]
SL digital output A
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[38]
Set dig. out. A high
is executed. The output goes low whenever the smart logic action
[32] Set dig. out.
A low
is executed.
[81]
SL digital output B
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[39]
Set dig. out. A high
is executed. The output goes low whenever the smart logic action
[33] Set dig. out.
A low
is executed.
[82]
SL digital output C
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[40]
Set dig. out. A high
is executed. The output goes low whenever the smart logic action
[34] Set dig. out.
A low
is executed.
[83]
SL digital output D
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[41]
Set dig. out. A high
is executed. The output goes low whenever the smart logic action
[35] Set dig. out.
A low
is executed.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
40 | Danfoss A/S © 2020.01