Option
Function
[70]
Logic rule 0
See
parameter group 13-4* Logic Rules
. If logic rule 0 is evaluated as true, the output goes high. Oth-
erwise, it is low.
[71]
Logic Rule 1
See
parameter group 13-4* Logic Rules
. If logic rule 1 is evaluated as true, the output goes high. Oth-
erwise, it is low.
[72]
Logic Rule 2
See
parameter group 13-4* Logic Rules
. If logic rule 2 is evaluated as true, the output goes high. Oth-
erwise, it is low.
[73]
Logic rule 3
See
parameter group 13-4* Logic Rules
. If logic rule 3 is evaluated as true, the output goes high. Oth-
erwise, it is low.
[74]
Logic rule 4
See
parameter group 13-4* Logic Rules
. If logic rule 4 is evaluated as true, the output goes high. Oth-
erwise, it is low.
[75]
Logic rule 5
See
parameter group 13-4* Logic Rules
. If logic rule 5 is evaluated as true, the output goes high. Oth-
erwise, it is low.
[80]
SL digital output A
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[38]
Set dig. out. A high
is executed. The output goes low whenever the smart logic action
[32] Set dig. out.
A low
is executed.
[81]
SL digital output B
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[39]
Set dig. out. B high
is executed. The output goes low whenever the smart logic action
[33] Set dig. out.
B low
is executed.
[82]
SL digital output C
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[40]
Set dig. out. C high
is executed. The output goes low whenever the smart logic action
[34] Set dig. out.
C low
is executed.
[83]
SL digital output D
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[41]
Set dig. out. D high
is executed. The output goes low whenever the smart logic action
[35] Set dig. out.
D low
is executed.
[84]
SL digital output E
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[42]
Set dig. out. E high
is executed. The output goes low whenever the smart logic action
[36] Set dig. out.
E low
is executed.
[85]
SL digital output F
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[43]
Set dig. out. F high
is executed. The output goes low whenever the smart logic action
[37] Set dig. out.
F low
is executed.
[90]
kWh counter pulse
Sends a pulse (200 ms pulse width) to output terminal whenever kWh counter changes (
parameter
15-02 kWh Counter
).
[98]
Virtual master dir.
NOTICE
This option is available only with software version 48.xx of the VLT® AutomationDrive FC 302.
A virtual master signal that controls the rotation direction of slaves.
[120]
Local ref active
Output is high when
parameter 313 Reference Site
=
[2] Local
.
Table 25: Local Reference Active
Reference site set in
parameter 3-13 Reference Site
Local reference active [120]
Remote reference active [121]
Reference site: Local
parameter 3-13 Reference Site [2] Local
1
0
Reference site: Remote
parameter 3-13 Reference Site [1] Remote
0
1
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 35
Danfoss A/S © 2020.01