The lower part of the cable clamp fixes the cable to the plate and provides strain relief. The upper part provides ~360°
grounding for the cable shield.
1
2
3
e3
0b
j1
47
.1
1
Figure 53: Stripping the Cable and Using the Grounding Plates
1
Stripping length, 10 mm (0.4 in)
2
Strain relief
3
Grounding
8.16
Connecting the Control Panel
1.
Connect the control panel to the terminal X9 in the modular control unit with a panel cable adapter.
8.17
Fiber Cable Requirements
The required fiber cable type is LC duplex cable assembly 0.5NA SI-POF.
The installation temperature of the fiber cable is -40...+85 °C (-40...+185 °F). The minimum bending radius is 25 mm (1.0 in).
Figure 54: Bending Radius of the Fiber Cables
1
Cable
2
Bending radius (25 mm, 1.0 in)
72
| Danfoss Drives Oy © 2024.03 AJ389643111587en-000101 / 172F6361A
Design Guide | iC7 Series Air-cooled System Modules