Table 42: Motor Cable Size Recommendations for Inverter Modules, 380–500 V
(continued)
Model code
Frame
I
N
[A]
Motor cable Cu
[mm
2
]
Motor cable Al
[mm
2
]
Maximum
terminal
cable size
[mm
2
]
(1)
Number of
grounding
terminals
(bolt size)
Maximum
number of
conductor
s per
phase
(bolt size)
iC7-60SAIN05-1000
1021
6x (3 x 95 + 50)
6x (3 x 120 + 41)
240Cu/Al
2/M8
6/M10
iC7-60SAIN05-1100
2xIM10
1123
6x (3 x 95 + 50)
6x (3 x 150 + 41)
240Cu/Al
2/M8
6/M10
iC7-60SAIN05-1260
1287
6x (3 x 120 + 70)
8x (3 x 120 + 41)
300Cu/Al
2/M8
8/M12
iC7-60SAIN05-1450
1481
8x (3 x 95 + 50)
8x (3 x 150 + 41)
300Cu/Al
2/M8
8/M12
iC7-60SAIN05-1710
2xIM11
1746
8x (3 x 120 + 70)
8x (3 x 185 + 57)
300Cu/Al
2/M8
8/M12
iC7-60SAIN05-1760
1797
9x (3 x 120 + 70)
12x (3 x 120 + 41)
300Cu/Al
3/M8
12/M12
iC7-60SAIN05-1960
2 001
9x (3 x 150 + 70)
12x (3 x 120 + 41)
300Cu/Al
3/M8
12/M12
iC7-60SAIN05-2150
2 195
9x (3 x 150 + 70)
12x (3 x 150 + 41)
300Cu/Al
3/M8
12/M12
iC7-60SAIN05-2510
3xIM11
2 563
12x (3 x 120 + 70)
12x (3 x 185 + 57)
300Cu/Al
3/M8
12/M12
1) The bolt hole spacing is 35 mm. Check the width of the cable lug.
10.4.4
Motor Cable Size Recommendations for Inverter Modules with Integration Units, 380–500 V
Table 43: Motor Cable Size Recommendations for Inverter Modules with Integration Units, 380–500 V
Model code
Frame
I
N
[A]
Motor cable Cu
[mm
2
]
Motor cable Al
[mm
2
]
Maximum
terminal
cable size
Number of
grounding
terminals
(bolt size)
Maximum
number of
conductor
s per
phase
(bolt size)
iC7-60SAIN05-385A
394
3x (3 x 50 + 25)
2x (3 x 120 + 41)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-480A
490
3x (3 x 70 + 35)
3x (3 x 120 + 41)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-590A
IR10
603
3x (3 x 95 + 50)
4x (3 x 95+ 29)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-658A
672
4x (3 x 70 + 35)
4x (3 x 120 + 41)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-730A
746
4x (3 x 95 + 50)
4x (3 x 150 + 41)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-820A
838
3x (3 x 150 + 70)
4x (3 x 150 + 41)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-880A
IR11
899
4x (3 x 120 + 70)
4x (3 x 185 + 57)
300 Cu/Al
1/M8
4/M10
iC7-60SAIN05-1000
1021
6x (3 x 95 + 50)
6x (3 x 120 + 41)
300 Cu/Al
2/M8
8/M10
iC7-60SAIN05-1100
2xIR10
1123
6x (3 x 95 + 50)
6x (3 x 150 + 41)
300 Cu/Al
2/M8
8/M10
120
| Danfoss Drives Oy © 2024.03 AJ389643111587en-000101 / 172F6361A
Design Guide | iC7 Series Air-cooled System Modules