Design Guide | iC7 Series Air-cooled System Modules
Table 46: Motor Cable Size Recommendations for Inverter Modules with Integration Units, UL 480 V
(continued)
Model code
Frame
I
N
[A]
Motor cable Cu
[mm
2
]
Motor cable
termination,
Panduit terminal
part number
Terminal
maximum
cable size
Number of
grounding
terminals
(bolt size)
Maximum
number of
conductor
s per
phase
(bolt size)
iC7-60SAIN05-658A
603
3 x 350MCM
LCAX350-12-X
500MCM
1 (M8)
4 (M10)
iC7-60SAIN05-730A
672
4 x 250MCM
LCAX250-12-X
500MCM
1 (M8)
4 (M10)
iC7-60SAIN05-820A
746
4 x 300MCM
LCAX300-12-X
500MCM
1 (M8)
4 (M10)
iC7-60SAIN05-880A
IR11
838
4 x 350MCM
LCAX350-12-X
500MCM
1 (M8)
4 (M10)
iC7-60SAIN05-1000
940
6 x 4/0
LCAX4/0-12-X
500MCM
2 (M8)
8 (M10)
iC7-60SAIN05-1100
2 x IR10
1052
6 x 250MCM
LCAX250-12-X
500MCM
2 (M8)
8 (M10)
iC7-60SAIN05-1260
1174
6 x 300MCM
LCAX300-12-X
500MCM
2 (M8)
8 (M10)
iC7-60SAIN05-1450
1328
8 x 250MCM
LCAX250-12-X
500MCM
2 (M8)
8 (M10)
iC7-60SAIN05-1710
2 x IR11
1603
8 x 350MCM
LCAX350-12-X
500MCM
2 (M8)
8 (M10)
iC7-60SAIN05-1760
1807
9 x 350MCM
LCAX350-12-X
500MCM
3 (M8)
12 (M10)
iC7-60SAIN05-1960
1 940
9 x 350MCM
LCAX350-12-X
500MCM
3 (M8)
12 (M10)
iC7-60SAIN05-2150
2 083
12 x 250MCM
LCAX250-12-X
500MCM
3 (M8)
12 (M10)
iC7-60SAIN05-2510
3 x IR11
2 389
12 x 300MCM
LCAX300-12-X
500MCM
3 (M8)
12 (M10)
10.5
Fuses
10.5.1
List of Fuse Size Information
The fuse size tables for the air-cooled system modules can be found with these links.
l
10.5.2 AC Fuses for AFE, 380–500 V AC
l
10.5.3 DC Fuses for AFE, 465–740 V DC
l
10.5.4 DC Fuses for Inverter Modules, 465–740 V DC
10.5.2
AC Fuses for AFE, 380–500 V AC
Table 47: AC Fuses for AFE, 380–500 V AC
Model code
(1)
Frame
Rated
current
I
L
[A]
Number
of fuses
Fuse
size
Mersen part
number
(2)
Fuse U
n
[V]
Fuse I
n
[A]
Minimu
m I
cp,mr
[A]
iC7-60SA3x05-317AE00
317
PC33UD69V550TF
690
550
3300
iC7-60SA3x05-400AE00
400
PC33UD69V550TF
690
550
3300
iC7-60SA3x05-514AE00
AM10/
AR10
514
3
33
PC33UD69V700TF
690
700
4800
Danfoss Drives Oy © 2024.03 AJ389643111587en-000101 / 172F6361A |