Table 51: Current Ratings for Regenerative AFE Module, 400 V AC (465–650 V DC)
(continued)
AC ratings
DC ratings
Model code
Frame
S
N
[kVA]
I
N
[A]
I
L
[A]
I
H
[A]
I
N-DC
[A]
P
L
[kW]
P
H
[kW]
iC7-60SA3A05-2800
1940
2859
2800
2231
3268
1902
1515
iC7-60SA3A05-3270
4 x
AM11/
AR11
2266
3338
3270
2710
3817
2221
1840
iC7-60SA3A05-3650
2529
3726
3650
2888
4260
2479
1961
iC7-60SA3A05-4080
5 x
AM11/
AR11
2827
4165
4080
3390
4761
2771
2302
iC7-60SA3A05-4500
3118
4594
4500
3544
5251
3056
2407
iC7-60SA3A05-4900
6 x
AM11/
AR11
3395
5002
4900
4070
5719
3327
2764
10.6.3
Current Ratings for Regenerative AFE Module, UL 480 V AC (650–740 V DC)
Table 52: Current Ratings for Regenerative AFE Module, UL 480 V AC (650–740 V DC)
AC ratings
DC ratings
Model code
Frame
S
N
[kVA]
I
N
[A]
I
L
[A]
I
H
[A]
I
N-DC
[A]
P
L
[kW]
P
H
[kW]
iC7-60SA3A05-317A
257
316
309
256
361
252
209
iC7-60SA3A05-400A
316
388
380
298
445
310
243
iC7-60SA3A05-514A
AM10/
AR10
385
473
463
385
542
378
314
iC7-60SA3A05-580A
433
531
520
424
608
424
346
iC7-60SA3A05-650A
487
598
585
470
684
477
383
iC7-60SA3A05-730A
541
664
650
511
759
530
417
iC7-60SA3A05-816A
AM11/
AR11
608
747
731
607
853
596
495
iC7-60SA3A05-920A
686
843
825
639
964
673
521
iC7-60SA3A05-1030
2 x
AM10/
AR10
774
950
930
770
1086
758
628
iC7-60SA3A05-1210
898
1103
1080
880
1262
880
717
iC7-60SA3A05-1410
1040
1276
1250
1030
1460
1019
840
iC7-60SA3A05-1630
2 x
AM11/
AR11
1214
1491
1460
1210
1705
1190
986
iC7-60SA3A05-1860
1389
1705
1670
1363
1949
1361
1111
iC7-60SA3A05-2120
1588
1950
1910
1533
2230
1557
1250
iC7-60SA3A05-2450
3 x
AM11/
AR11
1821
2236
2190
1820
2557
1785
1483
iC7-60SA3A05-2800
2087
2563
2510
1874
2930
2046
1527
iC7-60SA3A05-3270
4 x
AM11/
AR11
2428
2981
2920
2430
3408
2380
1980
128
| Danfoss Drives Oy © 2024.03 AJ389643111587en-000101 / 172F6361A