Design Guide | iC7 Series Air-cooled System Modules
Table 73: Ambient conditions
(continued)
Technical item or function
Technical data
Pollution degree
PD2
Altitude
0–4000 m (0–13100 ft) above sea level: in case network is not
corner-grounded (Voltage class 5).
Above 1000 m (3300 ft): derating of the output current by 1% per
each 100 m is required.
Vibration (IEC60068-2-6)
Displacement amplitude 0.5 mm (peak) at 5–22 Hz)
Maximum acceleration amplitude 1 G at 22–150 Hz
Shock (IEC60068-2-27)
maximum 4 G, 11 ms (in package)
Sound pressure level
1 system module in cabinet: 80 dB(A)
+3 dB(A) increase for every additional power unit
1) On board level on coated boards.
Table 74: EMC (IEC61800-3)
Technical item or function
Technical data
Immunity
Fulfills EN61800-3:2018, 1
st
and 2
nd
environment
Emissions
380–500 V AC: EN 61800-3 (2018), category C3, if the drive is in-
stalled according to instructions. See
All: The drive can be changed to C4 for IT type mains.
Table 75: Protections
Technical item or function
Technical data
Overvoltage trip limit
911 V DC
Undervoltage trip limit
Depends on mains voltage.
Mains voltage 400 V AC: trip limit 334 V DC
Mains voltage 500 V AC: trip limit 447 V DC
Ground fault protection
Yes
Mains supervision
Yes
Motor phase supervision
Yes
Overcurrent protection
Yes
Unit overtemperature protection
Yes
Motor overload protection
Yes
(1)
Motor stall protection
Yes
Motor underload protection
Yes
1) The motor overload protection activates at 110% of the full load current.
Danfoss Drives Oy © 2024.03 AJ389643111587en-000101 / 172F6361A |
147