Figure 18: Cabling Principle
1
Grounding bar of the control cable
2
Control cable
3
Grounding conductor
4
Mains cables
5
Motor cables
6
Strain relief
7
The grounding clamp, 360° grounding
6.5
Recommended Installation of Motor Cables
If the power units are connected in parallel without output filters or only with a common-mode filter, the recommended common
coupling point of motor cables is at the motor terminals. It is also possible to use an alternative installation method where the common
coupling point of the motor cables is near the drives. In this case, to avoid current imbalance, the installation must be symmetrical and
the tolerance of cable length (impedance) to common coupling point is maximum 5%. If the cable connections are not symmetrical, use
a dU/dt filter or a sine-wave filter.
34
| Danfoss Drives Oy © 2024.03 AJ389643111587en-000101 / 172F6361A
Design Guide | iC7 Series Air-cooled System Modules