SiUS372201EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
362
Note(s)
1. Infrared floor sensor PCB and connector
Diagnosis procedure 2
Infrared floor sensor error
(Error code
CE-02
)
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to
sensor and address data No. 26.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared floor
sensor PCB and the
connector (
1)
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
"--" by the above
verification
method.
Normal.
NO
Displays
CE-02
again or "--" for
sensor and
address data.
Replace the sensor.
Model
Infrared floor
sensor PCB
Connector
FXFQ-AA
A2P
X81A (A1P)
FXFQ-T
A3P
X2A (A2P)
FXZQ-TA
A4P
X110A (A6P)
FXZQ-TB
A4P
X81A (A1P)
FXUQ-P
A3P
X81A (A1P)
FXUQ-PA
A3P
X81A (A1P)
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...