Troubleshooting by Error Code
SiUS372201EB
317
Part 6 Service Diagnosis
Note(s)
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit control
PCB (A1P).
Replace the drain pump (M1P)
or check for dirt, etc.
YES
YES
NO
NO
The drain
pump works when the
power supply is reset for the
indoor unit.
The
voltage of
drain pump
terminals (
2) is in
accordance to the criteria
(
3) (within 5 minutes of
resetting the power
supply).
A
Model
1: Float switch (S1L) /
short circuit connector
2: Drain pump (M1P)
connector
3: Drain pump (M1P)
voltage
Note
FXFQ-AA
X15A
X25A
13 VDC
—
FXFQ-T
X15A
X10A
13 VDC
—
FXZQ-TA
X15A
X102A
13 VDC
—
FXZQ-TB
X15A
X25A
13 VDC
—
FXUQ-P
X15A
X25A
13 VDC
—
FXUQ-PA
X15A
X25A
13 VDC
—
FXEQ-P
X15A
X25A
13 VDC
—
FXDQ-M
X8A
X25A
220-240 VAC
—
FXSQ-TA
X15A
X25A
13 VDC
—
FXSQ-TB
X15A
X25A
13 VDC
—
FXMQ-PB
X15A
X25A
220-240 VAC
—
FXMQ-TB
X15A
X25A
13 VDC
—
FXMQ-TA
X15A
X25A
13 VDC
Option
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...