Field Settings for Indoor Unit
SiUS372201EB
231
Part 5 Field Settings and Test Operation
1. FXMQ54TB cannot be set to 150-200 Pa (0.60-0.80 inWG).
FXMQ-TB models
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
02
50 Pa (0.20 inWG)
03
60 Pa (0.24 inWG)
04
70 Pa (0.28 inWG)
05
80 Pa (0.32 inWG)
06
90 Pa (0.36 inWG)
07
100 Pa (0.40 inWG)
08
110 Pa (0.44 inWG)
09
120 Pa (0.48 inWG)
10
130 Pa (0.52 inWG)
11
140 Pa (0.56 inWG)
12
150 Pa (0.60 inWG) (
1)
13
160 Pa (0.64 inWG) (
1)
14
180 Pa (0.72 inWG) (
1)
15
200 Pa (0.80 inWG) (
1)
FXMQ-TA models
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
01
50 Pa (0.20 inWG)
02
75 Pa (0.30 inWG)
03
100 Pa (0.40 inWG)
04
115 Pa (0.46 inWG)
05
130 Pa (0.52 inWG)
06
150 Pa (0.60 inWG)
07
160 Pa (0.64 inWG)
08
175 Pa (0.70 inWG)
09
190 Pa (0.76 inWG)
10
200 Pa (0.80 inWG)
11
210 Pa (0.84 inWG)
12
220 Pa (0.88 inWG)
13
230 Pa (0.92 inWG)
14
240 Pa (0.96 inWG)
15
250 Pa (1.00 inWG)
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...