SiUS372201EB
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
244
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
Changing and access the setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds), you can select
the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
To quit and return to the initial status, press the
MODE (BS1)
button.
Changing the value of the selected setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds) you can
select the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
Now the
SET (BS2)
button is used to select the required value of the selected setting.
When the required value is selected, you can define the change of value by pressing the
RETURN (BS3)
button once.
Press the
RETURN (BS3)
button again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor
unit’s fan).
Mode: 2
Setting: 18
Make sure the segment indication is as during normal operation (default situation when shipped
from factory).
Press the
MODE (BS1)
button for over 5 seconds; result segment display:
Press the
SET (BS2)
button 18 times; result segment display:
Press the
RETURN (BS3)
button once; the value which is returned (depending on the actual
field situation), is the status of the setting. In the case of [2-18], default value is "0", which
means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is the current setting situation.
To change the value of the setting, press the
SET (BS2)
button until the required value appears
on the segment indication. When achieved, define the setting value by pressing the
RETURN
(BS3)
button once. To start operation according to the chosen setting, confirm again by
pressing the
RETURN (BS3)
button.
To leave the field setting, press the
MODE (BS1)
button once, you will return to the default
situation when shipped from factory.
Result: mode 2 accessed.
Result: mode 2 setting 18 is addressed.
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...