3.62.2 Inverter Radiation Fin Temperature Abnormality (Fan PCB)
Applicable
Models
All outdoor unit models
Error Code
P4
Sub code: 02, 03, 15, 16
Method of Error
Detection
Detects the resistance of the thermistor located inside the fan PCB circuit while the fan motor is not
in operation.
Error Decision
Conditions
The resistance of the thermistor comes to a value equivalent to open or short circuit.
Supposed
Causes
Defective fan PCB
Defective fan motor
Troubleshooting
The insulation
resistance of the relevant
fan motor is not more
than 1 M
.
Turn ON
the power supply.
Does the error
recur?
NO
YES
NO
YES
Replace the fan motor
(M1F, M2F).
Replace the fan PCB.
Continue operation.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check for fan PCB applicable to the error code
P4
while in
monitor mode.
P4-02/15: Fan PCB (M1F) Master / Sub
P4-03/16: Fan PCB (M2F) Master / Sub
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...