C6 - 02
Indoor blower does not have required parameters to
function
Refer to page 357.
U4 - 01
Indoor-outdoor transmission error
Refer to the
U4
flowchart.
UA - 13
Refrigerant type error
The type of refrigerant used for the indoor unit is different
from that used for the outdoor unit.
UA - 15
Not applicable for self-cleaning decoration panel
[when the self-cleaning decoration panel is mounted]
An outdoor unit is not applicable for the self-cleaning
decoration panel is connected.
UA - 17
Incorrect electric heater capacity setting
Refer to page 439.
UH - 05
Climate Talk Communication system combination error
(before initial setting for communication completes)
Refer to page 447.
UH - 06
Climate Talk Communication system combination error
(after initial setting for communication completes)
Refer to page 448.
Error code
Troubleshooting
Error Description
Diagnosis
F9 - 01
Branch Selector unit electronic expansion valve
abnormality
Refer to the
F9
flowchart and make a diagnosis based
on the Error code shown to the left.
F9 - 02
Branch Selector unit electronic expansion valve
abnormality
F9 - 05
Branch Selector unit electronic expansion valve
abnormality
Error code
Troubleshooting
Error Description
Diagnosis
E1 - 01
Outdoor unit PCB error
Refer to the
E1
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
E1 - 02
Defective outdoor unit PCB
E1 - 08
Outdoor unit sub PCB error (Master)
E1 - 09
Outdoor unit sub PCB error (Sub)
E2 - 01
Ground leakage detection error (Master)
Refer to the
E2
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
E2 - 02
Ground leakage detection error (Sub)
E2 - 06
Missing of ground leakage detection core (Master)
E2 - 07
Missing of ground leakage detection core (Sub)
E3 - 01
Activation of high pressure switch S1PH (Master)
Refer to the
E3
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
E3 - 02
High pressure sensor error (Master)
E3 - 03
Activation of high pressure switch S1PH (Sub)
E3 - 04
High pressure sensor error (Sub)
E3 - 07
High pressure standby E3 latch error (System integrated)
E3 - 13
Liquid stop valve check error (Master)
E3 - 14
Liquid stop valve check error (Sub)
E3 - 18
Overall retry of high pressure switch
E3 - 20
Activation of high pressure switch S2PH (Master)
E3 - 21
Activation of high pressure switch S2PH (Sub)
E4 - 01
Low pressure sensor error (Master)
Refer to the
E4
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
E4 - 02
Low pressure sensor error (Sub)
E5 - 01
Compressor M1C lock (Master)
Refer to the
E5
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
E5 - 02
Compressor M1C lock (Sub)
E5 - 07
Compressor M2C lock (Master)
E5 - 08
Compressor M2C lock (Sub)
Error code
Troubleshooting
Error Description
Diagnosis
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...