Troubleshooting by Error Code
SiUS372201EB
357
Part 6 Service Diagnosis
3.28 Indoor Blower Does Not Have Required Parameters to
Function
Applicable
Models
FXTQ-TA, FXTQ-TB
Error Code
C6-02
Outline
Indoor units perform required settings for control on the fan motor, but if the minimum required
settings are not made then information indicating as such will be included among the periodic
control status information.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the parameter information shows abnormality, it will be deemed abnormal operation.
At that point, parameter settings when initializing the fan motor will be implemented from the
beginning.
Error Reset
Conditions
If the parameter information is normal, the error will be cleared.
Supposed
Causes
Locked motor rotor condition
Corrective
Actions
Check for locked rotor condition.
Replace the indoor unit PCB or motor.
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...