Field Setting from Outdoor Unit
SiUS372201EB
269
Part 5 Field Settings and Test Operation
When heat pump lockout mode has been set the auto backup function will automatically be set.
This will allow the auxiliary or secondary heat source to be automatically energized in the event of a
system failure.
Error codes capable of auto backup are listed in the table below.
Please be aware that the error codes that are not listed do not auto backup in order to protect the
unit.
[2-79]:
Heat pump lockout release differential
Heat pump would be resumed when the outdoor air temperature is recovered by
differential (below) above the heat pump lockout temperature.
Heat pump lockout
release differential
Fahrenheit (°F)
Celsius (°C)
0
5
2.8
1 (default)
10
5.6
2
15
8.3
Error contents
Error code
(Auto backup possible)
Activation of high pressure switch
E3
Activation of low pressure sensor
E4
Compressor motor lock
E5
Compressor damage alarm
E6
Outdoor fan motor abnormality
E7
Electronic expansion valve coil abnormality
E9
Four way valve abnormality
Opposite air conditioning alarm
EA
Box air thermistor abnormality
H1
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H3
Outdoor fan PCB abnormality
H7
Outdoor air thermistor abnormality
H9
Discharge pipe temperature abnormality
F3
Wet alarm
F4
Branch Selector unit electronic expansion valve abnormality
F9
Discharge pipe thermistor abnormality
Compressor body thermistor abnormality
J3
Compressor suction thermistor abnormality
Suction pipe before accumulator thermistor abnormality
J5
Heat exchanger deicer thermistor abnormality
Heat exchanger gas pipe thermistor abnormality
J6
Receiver inlet thermistor abnormality
Subcooling heat exchanger liquid pipe thermistor abnormality
Subcooling injection thermistor abnormality
J7
Heat exchanger liquid pipe thermistor abnormality
J8
Subcooling heat exchanger gas pipe thermistor abnormality
Receiver gas purge thermistor abnormality
Electrical box air outlet thermistor abnormality
J9
High pressure sensor abnormality
JA
Low pressure sensor abnormality
JC
Inverter PCB abnormality
L1
Inverter radiation fin temperature rise abnormality
L4
Compressor instantaneous overcurrent
L5
Compressor overcurrent
L8
Compressor startup abnormality
L9
Transmission error between inverter and outdoor unit main PCB
LC
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...