Field Setting from Outdoor Unit
SiUS372201EB
257
Part 5 Field Settings and Test Operation
[2-21]:
Refrigerant recovery/vacuuming mode
In order to achieve a free pathway to recovering refrigerant out of the system or to
remove residual substances or to vacuum the system it is necessary to apply a
setting which will open required valves in the refrigerant circuit so the recovering of
refrigerant or vacuuming process can be done properly.
Default value: 0
To activate this function, change [2-21] to 1.
To stop the refrigerant recovery/vacuuming mode, press the
RETURN (BS3)
button.
If the
RETURN (BS3)
button is not pressed, the system will remain in refrigerant
recovery/vacuuming mode.
[2-22]:
Automatic night-time low noise setting and level during night-time
By changing this setting, you can activate the automatic night-time low noise
operation function of the unit and define the level of operation. Depending on the
chosen level, the noise level will be lowered (3: Level 3 < 2: Level 2 < 1: Level 1).
The start and stop moments for this function are defined under setting [2-26] and
[2-27].
Default value: 0
Change [2-22] to 1, 2 or 3 in function of required level.
[2-25]:
Night-time low noise operation level via the external control adaptor
If the system needs to run under night-time low noise operation conditions when an
external signal is sent to the unit, this setting defines the level of night-time low noise
that will be applied (3: Level 3 < 2: Level 2 < 1: Level 1).
This setting will only be effective when the optional external control adaptor
(DTA104A62) is installed and the setting [2-12] is activated.
Default value: 2
Change [2-25] to 1, 2 or 3 in function of required level.
[2-26]:
Night-time low noise operation start time
Change [2-26] to 1, 2 or 3 in function of required timing.
Default value: 2
Value
[2-26]
Start time automatic night-time low noise
operation (approximately)
1
About 8:00 PM
2 (default)
About 10:00 PM
3
About 12:00 AM
This setting is used in conjunction with setting [2-22].
[2-27]:
Night-time low noise operation stop time
Default value: 3
Value
[2-27]
Stop time automatic night-time low noise
operation (approximately)
1
About 6:00 AM
2
About 7:00 AM
3 (default)
About 8:00 AM
This setting is used in conjunction with setting [2-22].
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...