Field Setting from Outdoor Unit
SiUS372201EB
265
Part 5 Field Settings and Test Operation
Note(s)
In high humid areas, it is recommended to keep this setting to 0 or 1.
[2-90]:
Indoor unit without power
U4
error generation.
In case an indoor unit needs maintenance or repair on the electric side, it is possible
to keep the rest of the
VRV
DX indoor units operating without power supply to some
indoor unit(s).
Default value: 0 (not active)
Field setting 1: It is possible to operate system without
U4
error when some indoor
units are temporarily without power supply.
Field setting 2: It is possible to operate system with
U4
warning when some indoor
units are temporarily without power supply.
Following conditions need to fulfil:
Maximum equivalent piping length of the farthest indoor less than 120 m (394 ft).
Index indoor units power simultaneously less than 30% of the nominal outdoor.
Total capacity is less than 30% of the nominal one of the outdoor unit.
Operation time is limited to 24 hours period.
It is recommended to shut down connected indoor units at the same floor.
Not possible to use service mode operation (e.g. recovery mode).
Backup operation has priority over this special feature.
[2-92]:
Te target temperature upper limit
Default value: 1.
Value
[2-92]
Te target temperature upper limit
0
L
1 (default)
M
2
H
If Auto Te, then use this setting to address different load profiles. If the frequent operation is at
lower system load, then use a higher setting under [2-92].
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...