Troubleshooting by Error Code
SiUS372201EB
323
Part 6 Service Diagnosis
3.8.3 Indoor Fan Motor Abnormality (FXSQ54TA, FXSQ54TB, FXMQ15-54PB,
FXMQ30-54TB, FXMQ-TA Models)
Applicable
Models
FXSQ54TA, FXSQ54TB, FXMQ15-54PB, FXMQ30-54TB, FXMQ-TA
Error Code
A6
Method of Error
Detection
Error from the current flow on the fan PCB
Error from the rotation speed of the fan motor in operation
Error from the position signal of the fan motor
Error from the current flow on the fan PCB when the fan motor starting operation
Error Decision
Conditions
An overcurrent flows.
The rotation speed is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.
Supposed
Causes
Clogging of a foreign matter
Disconnection of the fan motor connectors (X1A and X2A)
Disconnection of the connectors between the indoor unit control PCB (A1P) and fan PCB (A2P)
Defective fan PCB (A2P)
Defective fan motor
Summary of Contents for VRV EMERION REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Page 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Page 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Page 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Page 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...