2
|
Components
Service manual
70
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
Is the correct spare part for the indoor
unit PCB installed?
Action
No
Replace the indoor unit PCB, see
To check the wiring of the indoor unit main PCB
Prerequisite:
First perform all earlier checks of the indoor unit PCB, see
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
137].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
68] of the indoor unit
PCB and continue with the next
procedure.
To check the fuse of the indoor unit main PCB
Prerequisite:
First perform all earlier checks of the indoor unit PCB, see
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a
Fuse
Blown fuse on the indoor unit PCB?
Action
Yes
Replace the blown fuse, see