2
|
Components
Service manual
118
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
Does the measured resistance of the
thermistor match with the
temperature determined resistance?
Action
Yes
Thermistor is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
No
Replace the specific PCB, see
To perform an electrical check of the fin thermistor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Locate the thermistor on the appropriate PCB.
2
Measure the temperature using a contact thermometer.
INFORMATION
The thermistors may vary according to the specific unit.
3
Determine the thermistor resistance that matches the measured
temperature.
Type 1 thermistor
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
–20
197.81
10
39.96
40
10.63
70
3.44
–19
–18
–17
–16
–15
–14
–13
–12
–11
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
11
12
13
14
15
16
17
18
19
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
41
42
43
44
45
46
47
48
49
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
71
72
73
74
75
76
77
78
79
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
–10
111.99
20
25.01
50
7.18
80
2.47