3
|
Third party components
Service manual
128
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To replace the clogged/leaking part of the refrigerant circuit
1
See the correct procedure for the component that needs to be repaired. See
also
129] for more details.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To recuperate the refrigerant
Prerequisite:
Stop the unit operation via the user interface.
1
Manually open all expansion valves.
2
Connect the vacuum pump, manifold, recovery unit, and refrigerant bottle to
the service port of the refrigerant circuit as shown below.
H
V
R
L
c
b
a
a
Vacuum pump
b
Connect flexible hose to service port
c
To recovery pump
L
Low pressure
H
High pressure
V
Vacuum
R
Refrigerant
3
Is the problem solved?
Action
Yes
No further actions required.