2
|
Components
Service manual
53
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
4
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
5
Wrap a wet rag around the compressor pipes and solder the compressor pipes
to the refrigerant pipes.
a
a
a
Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
6
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
7
Connect the Faston connectors to the compressor wire terminals U, V and W
a
a
a
a
Faston connector
8
Install the cover of the compressor wire terminals.