DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
7
Check that the DC fan motor connector is properly connected to the PCB.
8
Unplug the DC fan motor connector and measure the resistance on the
connector pins shown below. The measured resistance MUST be:
VDC
Comm
Resistance
1
4
71~79 Ω
1
7
4
7
10 (GND)
1
OL
4
7
11
1.96 kΩ
12
10.9 kΩ
13
INFORMATION
The measured resistance values may deviate from the listed values due to instability
during the measurements.
Are the measured resistance values
correct?
Action
Yes
Continue with the next step.
No
9
With the DC fan motor connector S71 disconnected from the main PCB,
measure the voltage on the connector pins 10-11 (= fan motor control) on the
inverter PCB.
Result:
The voltage MUST be 15±10% V DC.
Is the measured voltage correct?
Action
Yes
Continue with the next step.
No
Perform a check of the main PCB, see
10
Manually (slowly) rotate the fan blade propeller 1 turn and measure the
voltage on the DC fan motor connector pins 10-12.
Result:
4 pulses MUST be measured.
11
Repeat the previous step and measure the voltage on the DC fan motor
connector pins 10-13.
Result:
4 pulses MUST be measured.