Components
Service manual
60
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
CAUTION
Overheating the valve will damage or destroy it.
4
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body
INFORMATION
The expansion valve and motor can have a different configuration / layout.
5
Reinstall the putty.
6
To install the expansion valve motor, see
7
Add
refrigerant
to
the
refrigerant
circuit,
see
About the installation of the expansion valve motor
NOTICE
Select the correct type.
To install the expansion valve motor with clip
1
Install the expansion valve motor on the expansion valve body.