Components
Service manual
80
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
a
a
b
b
a
a
Screw
b
PCB support
3
Install and tighten the screws.
4
Connect all connectors to the main PCB.
INFORMATION
Use the wiring diagram and connection diagram for correct installation of the
connectors, see
137].
Is the problem solved?
Action
Yes
No further actions required.
No
75] of the PCB and
continue with the next procedure.
To remove a fuse of the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Remove the fuse from the PCB.
a
a
Fuse
2
To install a fuse on the main PCB, see