Tightening torque

The sizes of the shutoff valves on each model and the tightening torque 
for each size are listed in the table below.

<Size of Shutoff Valve>

(Refer to figure 28)

1.

Service port

2.

Cap

3.

Hex holes

4.

Shaft (valve body)

5.

Seal section 

To open

1.

Remove the cap and turn the shaft counterclockwise with the hexa-
gon wrench.

2.

Turn it until the shaft stops.

3.

Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)

To close

1.

Remove the cap and turn the shaft clockwise with the hexagon wrench.

2.

Securely tighten the valve until the shaft contacts the main body seal.

3.

Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)

<Tightening torque>

[How to Check How Many Units are Connected]

It is possible to find out how many indoor or outside unit in the system are turned on by operating the push button on the PC-board (A1P) of outside 
unit (In case of multi system master unit).
Follow the procedure below to check how many indoor or outside units are turned on.

NOTE

Press the “MODE button” (BS1) if you get confused while operating.
This returns to 

Setting Mode 1 

(H1P : OFF, default).

11-2 Procedure of Adding Refrigerant charging and 

check operation

WARNING

Electric Shock Warning

Make sure to close the EL. COMPO. BOX lid before turning on the 
power.

Perform the setting on the PC-board (A1P) of the outside unit and 
check the LED display after the power is on via the inspection door 
which is in the EL. COMPO. BOX lid.

(Refer to figure 29)

1.

EL. COMPO. BOX (1)

2.

Inspection door

3.

EL. COMPO. BOX (1) lid

4.

LED (H1~8P)

5.

Push button(BS1~5)

6.

Lift the protruding part to open the inspection door.

72PA type

96PA type

108PA type

Liquid pipe 
shutoff valve

φ

3/8

The 108PA type corresponds to the 

φ

1/2 - diameter 

onsite piping using the accessory pipe.

Low side 
equalizer pipe 
shutoff valve

φ

1

All  types corresponds to the 

φ

3/4 - diameter onsite 

piping using the accessory pipe.

Gas shutoff 
valve

φ

3/4

The 72PA type corresponds to the 

φ

3/4 - diameter 

onsite piping using the accessory pipe.
The 96PA type corresponds to the 

φ

7/8 - diameter 

onsite piping using the accessory pipe.
The 108PA type corresponds to the 

φ

1-1/8 - diameter 

onsite piping using the accessory pipe.

High side 
equalizer pipe 
shutoff valve

φ

3/4

Shutoff 
valve size

Tightening torque ft · lbf (Turn clockwise to close)

Shaft (valve body)

Cap (valve lid) Service port

φ 

3/8

3.98 - 4.87

Hexagonal 

wrench 4mm

9.95 - 12.17

8.48 - 10.3

φ 

1/2

5.97 - 7.30

13.3 - 16.2

φ 

3/4

19.9 - 24.3

Hexagonal 

wrench 8mm

16.6 - 20.3

φ 

1

(LED display: 

h

 ...OFF  

i

 ...ON  

j

 ...Blinking  

 ...Uncertain)

LED display

H1P

H2P

H3P

H4P

H5P

H6P

H7P

(1) Press the MODE button (BS1) once at 

Setting Mode 1

 (H1P : off), and set the MON-

ITOR MODE (H1P : Blinking).

j

h

h

h

h

h

h

(2) Press the SET button (BS2) the number of times until the 

LED display matches that at right.

For checking the number of 
outside units : eight times

j

h

h

i

h

h

h

For checking the number 
of indoor units : five times

j

h

h

h

i

h

i

(3) Press the RETURN button (BS3) and read the number of units from the display of 

H2P through H7P.
[Reading Method]
The display of H2P through H7P should be read as a binary number, with 

j

 standing 

for “1” and 

h

 standing for “0”.

j

j

h

j

h

j

j

h

(4) Press the MODE button (BS1) once. This returns to 

Setting Mode 1 

(H1P : OFF, default).

h

h

i

h

h

h

h

Ex: For the LED display at right, this would be “0 1 0 1 1 0 ”, 
which would mean 22 units are connected.

Note: “000000” indicates 64 units.

32 × 

0

 + 16 × 

1

 + 8 × 

0

 + 4 × 

1

 + 2 × 

1

 + 1 × 

0

 = 22 units

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...