1-3 Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and eventual 
other parts, should be done in accordance with the relevant local and 
national regulations.

2.

INTRODUCTION

RXYQ-PA series are designed for outdoor installation and used for 
cooling and heating applications.

The indoor units that combined with RXYQ-PA system for air condi-
tioning are Daikin VRV series indoor units that compatible with 
R410A. To learn which indoor units are compatible with R410A, refer 
to the product catalogs. To combine with other refrigerant indoor unit 
will cause malfunction.

2-1 Combination

The system name and that independent units are as follows.

The system name

〉             〈

Independent units

RXYQ72PAYD/PATJ ...... RXYQ72PAYD/PATJ
RXYQ96PAYD/PATJ ...... RXYQ96PAYD/PATJ
RXYQ108PAYD/PATJ .... RXYQ108PAYD/PATJ
RXYQ144PAYD/PATJ .... RXYQ72PAYD/PATJ

RXYQ72PAYD/PATJ

RXYQ168PAYD/PATJ .... RXYQ72PAYD/PATJ

RXYQ96PAYD/PATJ

RXYQ192PAYD/PATJ .... RXYQ96PAYD/PATJ

RXYQ96PAYD/PATJ

The indoor units can be installed in the following range.

Outside unit

〉                  〈

Total capacity index of indoor units

RXYQ72PAYD/PATJ ...... 43 ~ 93.5
RXYQ96PAYD/PATJ ...... 57.5 ~ 124.5
RXYQ108PAYD/PATJ .... 64.5 ~ 140
RXYQ144PAYD/PATJ .... 86 ~ 187
RXYQ168PAYD/PATJ .... 100.5 ~ 218
RXYQ192PAYD/PATJ .... 115 ~ 249.5

For installing the 2 units multi system, Outside unit multi connection 
piping kit “BHFP22P100U” are required.

If the total capacity of the connected indoor units exceeds the capac-
ity of the outside unit, cooling and heating performance may drop 
when running the indoor units. See the capacity table in the Engi-
neering Data Book for details.

2-2 Standard supplied accessories

Confirm the following accessories are included. The storage location of 
the accessories is shown in figure 1.

NOTE

Do not throw away any of the accessories until installation is complete. 
They are needed for installation work.

(Refer to figure 1)

1.

Clamps, Manuals, etc.

2.

Accessory pipes

2-3 Option accessory

To install the outside units, the following optional parts are also required. 
To select an optimum kit, refer to “

6. REFRIGERANT PIPING

”.

Outside unit multi connection piping kit

Refrigerant branching kit 

Make sure that any separately purchased accessories are designed for 
use with R410A.

2-4 Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of specifications.

2-5 Main components

For main components and function of the main components, refer to the 
Engineering Data Book.

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions and 
get the customer’s permission.

1.

Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.

2.

The foundation is strong enough to support the weight of the unit and 
the floor is flat to prevent vibration and noise generation.

3.

The piping length between the outside unit and the indoor unit may 
not exceed the allowable piping length.
(Refer to

  “6. REFRIGERANT PIPING”

)

4.

Locations where the unit’s suction vent and outlet vent do not gener-
ally face the wind.
Wind blowing directly into the suction or outlet vents will interfere with 
the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

Number of outside units connected

2 units

Kit name

BHFP22P100U

REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73HU
REFNET joint

KHRP26M22T

KHRP26M33T

KHRP26M72TU KHRP26M73TU

Shape

Liquid side
accessory
pipe (1)

High side
equalizer
accessory
pipe (1)

High side
equalizer
accessory
pipe (2)

Low side
equalizer
accessory
pipe (1)

Low side
equalizer
accessory
pipe (2)

L type
accessory
joint (1)

L type
accessory
joint (2)

Liquid side
accessory
pipe (2)

Gas side accessory pipe (1)

Gas side accessory
pipe (2)

1 pc.

1 pc.

1 pc.

72PA type

Quantity

Shape

Name

Name

2 pcs.

96PA type

72PA type

96PA type

108PA type

108PA type

1 pc.

1 pc.

1 pc.

1 pc.

Quantity

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

φ

3/4

φ

7/8

O.D 

φ

1

I.D 

φ

1

φ

1

φ

1-1/8

φ

7/8

φ

1

φ

3/4

φ

1

φ

3/4

(Large)

(Small)

2 pcs.

1 pc. about each item

Clamp(2)

1 pc.

Clamp(3)

Clamp(1)

8 pcs.

4 pcs.

Vinyl tube

2 pcs.

2 pcs.

Conduit mounting plate

Quantity

Name

Manuals, etc.

Shape

 Operation manual

 Installation manual

 “REQUEST FOR THE 

INDICATON” label 
(Installation records)

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: