background image

13

English

When two wires are connected to a single terminal, connect them so 
that the rear sides of the crimp contacts face each other. Also, make 
sure the thinner wire is on top, securing the two wires simultaneously 
to the resin hook using the included clamp (1).

7-6 Procedure for Wiring Inside Units

Referring to figure 24, secure and wire the power and transmission 
wiring using the included clamp (1), (2), and (3).

Wire so that the ground wiring does not come into contact with the 
compressor lead wiring.
If they touch, this may have an adverse effect on other devices.

The transmission wiring must be at least 2 in. away from the power wiring.

Make sure all wiring do not contact to the pipes (hatching parts in the 
figure 24).

(Refer to figure 24)

1.

Retain with accessory clamp (3).

2.

Electric conduit

3.

When routing out the power/ground wires from the left side.

4.

When routing out the transmission wiring from the opening 
for piping.

5.

When routing out the power/ground wires from the front.

6.

Clear over 2 in..

7.

When routing out the transmission wiring from the knockout 
hole.

8.

Retain to the back of the column support with the accessory 
clamp (2).

9.

When routing out the power/ground wires from the right side.

10.

Power wiring

11.

Transmission wiring

12.

Ground wire

Precautions when knocking out knockout holes

To punch out a knockout hole, hit it with a hammer.

Open an appropriate hole as needed.

After knocking out the holes, trim off the burr, then we recommend 
you  to paint the edges and areas around the edges using the repair 
paint to prevent rusting.

Power line : Open a knockout hole as shown at left and connect 
it using a conduit.

Transmission line : Connect it using a conduit in the knockout hole 
on the right.

NOTE

After wiring work is completed, check to make sure there are no loose 
connections among the electrical parts in the EL.COMPO.BOX.

8.

AIR TIGHT TEST AND VACUUM DRYING

 After finished piping work, carry out air tight test and vacuum drying.

NOTE

Always use nitrogen gas for the airtightness test.

Absolutely do not open the shutoff valve until the main power ciruit 
insulation measurement has been completed. (measuring after the 
shutoff valve is opened will cause the insulation value to drop.)

<Needed tools>

<The system for air tight test and vacuum drying>

Referring to figure 25, connect a nitrogen tank, refrigerant tank, and 
a vacuum pump to the outside unit.
The refrigerant tank and the charge hose connection to refrigerant 
charge port or the valve A in figure 25 are needed in 

“11. ADDI-

TIONAL REFRIGERANT CHARGE AND CHECK OPERATION”

.

(Refer to figure 25)

1.

Gauge manifold

2.

Nitrogen

3.

Measuring device

4.

R410A tank (with siphon)

5.

Vacuum pump

6.

Charge hose

7.

High side equalizer pipe shutoff valve

8.

Gas pipe shutoff valve

9.

Low side equalizer pipe shutoff valve

10.

Liquid pipe shutoff valve

11.

Refrigerant charge port

12.

Valve A

13.

Valve B

14.

Valve C

15.

Outside unit

16.

Indoor unit

17.

Shutoff valve

18.

Service port

19.

Field piping

20.

Gas flow

NOTE

The air-tightness test and 
vacuum drying should be 
done using the service 
ports of equalizer pipe, gas 
pipe and liquid pipe shutoff 
valve.
See the [R410A] Label 
attached to the front plate 
of the outside unit for 
details on the location of 
the service port (see figure 
at right)

See 

[Shutoff valve operation procedure] 

in 

“11-1 Before work-

ing”

 for details on handling the shutoff valve.

The refrigerant charge port is connected to unit pipe.
When shipped, the unit contains the refrigerant, so use caution when 
attaching the charge hose.

Terminal 
block

Crip style 
terminal

Wire : narrow

Wire : thick

Resin hook

Burr

Knockout hole

Left side

Right side

Conduit 
(field supply)

Lock nut 
(field supply)

Conduit mounting plate 
(accessory)

Gauge manifold
Charge hose 
valve

To prevent entry of any impurities and insure 
sufficient pressure resistance, always use the 
special tools dedicated for R410A.

Use charge hose that have pushing stick for 
connecting to service port of shutoff valves or 
refrigerant charge port.

Vacuum pump

The vacuum pump for vacuum drying should 
be able to lower the pressure to –14.6 psi.

Take care the pump oil never flow backward 
into the refrigerant pipe during the pump stops.

[R410A] Label

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: