background image

11

English

7.

FIELD WIRING

NOTE

All field wiring and components must be installed by a licensed elec-
trician and must comply with relevant local and national regulations.

Be sure to use a dedicated power circuit. Never use a power supply 
shared by another appliance.

Never install a phase advancing capacitor. As this unit is equipped 
with an inverter, installing a phase advancing capacitor will not only 
deteriorate power factor improvement effect, but also may cause 
capacitor abnormal heating accident due to high-frequency waves.

Only proceed with wiring work after blocking off all power.

Always ground wires in accordance with relevant local and national 
regulations.

This machine includes an inverter device. Connect earth and leave 
charge to eliminate the impact on other devices by reducing noise 
generated from the inverter device and to prevent leaked current 
from being charged in the outer hull of the product.

Do not connect the ground wire to gas pipes, sewage pipes, lightning 
rods, or telephone ground wires.

Gas pipes :

 can explode or catch fire if there is a gas leak.

Sewage pipes :

 no grounding effect is possible if hard plastic piping 

is used.

Telephone ground wires and lightning rods :

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit breaker 
that be capable of handling high harmonics in order to prevent mal-
functioning of the earth leakage circuit breaker itself.

Earth leakage circuit breaker which are especially for protecting 
ground-faults should be used in conjunction with main switch or fuse 
for use with wiring.

Electrical wiring must be done in accordance with the wiring dia-
grams and the description herein.

Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may 
be broken down.)

Never remove thermistor, sensor or etc. when connecting power wir-
ing and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compressor 
may be broken down.)

This product have reversed phase protection detector that only 
works when the power is turned on. If there exists blackout or the 
power goes on and off which the product is operating, attach a 
reversed phase protection circuit locally. Running the product in 
reversed phase may break the compressor and other parts.

Attach the power wire securely. Introducing power with a missing N-
phase or with a mistaken N-phase will break the unit.

Never connect the power supply in reversed phase. 
The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.

Make sure the electrical unbalance ratio is no greater than 2%. If it is 
larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction 
code will be displayed on the indoor remote controller.

Connect the wire securely using designated wire and fix it with attached 
clamp without applying external pressure on the terminal parts (terminal 
for power wiring, terminal for transmission wiring and earth terminal).

If there exists the possibility of reversed phase, lose phase, momen-
tary blackout or the power goes on and off while the product is oper-
ating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor 
and other parts.

7-1 Power circuit, safety device and cable

requirements

A power circuit (see the following table) must be provided for connec-
tion of the unit. This circuit must be protected with the required safety 
devices, i.e. a main switch, a slow blow fuse on each phase and an 
earth leakage circuit breaker.

When using residual current operated circuit breakers, be sure to 
use a high-speed type (0.1 second or less) 200mA rated residual 
operating current.

Use copper conductors only.

Use insulated wire for the power cord.

Select the power supply cable type and size in accordance with rel-
evant local and national regulations.

Specifications for local wiring power cord and branch wiring are in 
compliance with local cord.

7-2 Wiring Connection Example for Whole System

(Refer to figure 17)

1.

Power supply

2.

Main switch

3.

Earth leakage circuit breaker

4.

Fuse

5.

Outside unit

6.

Remote controller

7.

Indoor unit

NOTE

Make sure the weak electric wiring (i.e. for the remote controller, between 
units, etc.) and the power wiring do not pass near each other, keeping 
them at least 2 in. apart.
Proximity may cause electrical interference, malfunctions, and breakage.

Be sure to connect the power wiring to the power wiring terminal 
block and secure it as described in “

7-5 Power Wiring Connection 

Procedure

”.

Transmission wiring should be secured as described in “

7-4 Trans-

mission Wiring Connection Procedure

”.

Secure wiring with clamp such as insulation lock ties to avoid contact 
with piping.

Shape the wires to prevent the structure such as the EL. COMPO. 
BOX lid deforming. And close the cover firmly.

All field wiring is to be procured on site.

7-3 Leading wire Procedure

The power wiring and ground wiring are passed out from the power 
wiring hole on the sides, the front (knock hole) or the bottom frame 
(knock hole) .

The transmission wiring is passed out from the wiring hole (knock 
hole) on the front of the unit or from a piping hole.

(Refer to figure 18-1)

1.

Electric wiring diagram
Printed on the back of the EL. COMPO. BOX lid.

2.

Knockout hole

3.

Power line

4.

Transmission line

(Refer to figure 18-2)

1.

EL. COMPO. BOX lid

2.

Service lid

3.

[Service precautions] Label location

Phase and

frequency

Voltage

Minimum

circuit amp.

Recom-

mended fuses

Transmission 

line selection

RXYQ72PAYD

φ

 3, 60Hz

460V

20.2A

25A

AWG18-16

RXYQ96PAYD

φ

 3, 60Hz

460V

20.3A

25A

AWG18-16

RXYQ108PAYD

φ

 3, 60Hz

460V

20.5A

30A

AWG18-16

RXYQ144PAYD

φ

 3, 60Hz

460V

40.4A

25A+25A

AWG18-16

RXYQ168PAYD

φ

 3, 60Hz

460V

40.5A

25A+25A

AWG18-16

RXYQ192PAYD

φ

 3, 60Hz

460V

40.6A

25A+25A

AWG18-16

RXYQ72PATJ

φ

 3, 60Hz

208-230V

36.1A

40A

AWG18-16

RXYQ96PATJ

φ

 3, 60Hz

208-230V

36.1A

50A

AWG18-16

RXYQ108PATJ

φ

 3, 60Hz

208-230V

41.3A

60A

AWG18-16

RXYQ144PATJ

φ

 3, 60Hz

208-230V

72.2A

40A+40A

AWG18-16

RXYQ168PATJ

φ

 3, 60Hz

208-230V

72.2A

40A+50A

AWG18-16

RXYQ192PATJ

φ

 3, 60Hz

208-230V

72.2A

50A+50A

AWG18-16

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: