background image

English

4

5.

The space around the unit is adequate for servicing and the mini-
mum space for air inlet and air outlet is available.
(See the 

“Installation Space Examples”

 for the minimum space 

requirements.)

Installation Space Examples

The installation space requirement shown in figure 2 is a reference 
for cooling operation when the outdoor temperature is 95°F. 
If the design outdoor temperature exceeds 95°F or the heat load 
exceeds maximum capacity in all the outside unit, take an even large 
space on the intake shown in figure 2.

During installation, install the units using the most appropriate of the 
patterns shown in figure 2 for the location in question, taking into 
consideration human traffic and wind.

If the number of units installed is more than that shown in the pattern 
in figure 2, install the units so there are no short circuits.

As regards space in front of the unit, consider the space needed for 
the local refrigerant piping when installing the units.

If the work conditions in figure 2 do not apply, contact your dealer or 
Daikin directly.

(Refer to figure 2)

1.

Front side

2.

No limit to wall height

3.

Service space of front side

4.

Service space of suction side

For Patterns 1 and 2 in figure 2 :

Wall height for front side – no higher than 59 in.

Wall height on the suction side – no higher than 19-5/8 in.

Wall height for sides – no limit.

If the height is exceeded the above, calculate h1 and h2 shown in 
the figure below, and add h2/2 to the service space of front side 
and h1/2 to the service space of suction side.

DANGER

• Do not install unit in an area where flammable materials are 

present due to risk of explosion resulting in serious injury or 
death.

• Refrigerant gas in heavier air and replaces oxygen. A massive 

leak could lead to oxygen depletion, especially in basements, 
and an asphyxiation hazard could occur leading to serious inju-
ry or death.
Refer to the chapter “CAUTION FOR REFRIGERANT LEAKS”.

NOTE

1.

An inverter air conditioner may cause electronic noise generated 
from AM broadcasting. Examine where to install the main air condi-
tioner and electric wires, keeping proper distances away from stereo 
equipment, personal computers, etc. 
Particularly for locations with weak reception, ensure there is a dis-
tance of at least 10 ft for indoor remote controllers, place power wir-
ing and transmission wiring in conduits, and ground the conduits.

 (Refer to figure 3)

1.

Indoor unit

2.

Branch switch, earth leakage circuit breaker

3.

Remote controller

4.

COOL/HEAT selector

5.

Personal computer or radio

2.

When installing in locations where there is heavy snowfall, imple-
ment the following snow measures.

Ensure the base is high enough that intakes are not clogged by 
snow.

Remove the rear intake grille to prevent snow from accumulating 
on the fins.

4.

INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage should 
be reported immediately to the carrier claims agent.

When handling the unit, take into account the following :

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

2.

Decide on the transportation route.

3.

If a forklift is to be used, pass the forklift arms through the large open-
ings on the bottom of the unit. 

(Refer to figure 4)

4.

If hanging the unit, use a cloth sling to prevent damaging the unit. 
Keeping the following points in mind, hang the unit following the pro-
cedure shown in figure 5.

Use a sling sufficiently strong to hold the mass of the unit.

Use 2 belts of at least 27 ft long.

Place extra cloth or boards in the locations where the casing 
comes in contact with the sling to prevent damage. 

Hoist the unit making sure it is being lifted at its center of gravity.

5.

After installation, remove the transportation brackets (yellow) 
attached to the large openings. 

(Refer to figure 4)

(Refer to figure 4)

1.

Packaging material

2.

Forklift

3.

Removal of shipping brackets

4.

Shipping bracket (Remove the brackets by pushing the hook.)

(Refer to figure 5)

1.

Belt sling

2.

Wear plate

5.

PLACING THE UNIT

Make sure the unit is installed level on a sufficiently strong base to 
prevent vibration and noise. 

(Refer to figure 6)

The base should support the unit with the extent larger than hatched 
area in figure 7.
If protective rubber is to be attached, attach it to the whole face of the 
base.

The height of the base should be at least 5-7/8 in. from the floor.

Secure the unit to its base using foundation bolts. (Use four commer-
cially available M12-type foundation bolts, nuts, and washers.)

The foundation bolts should be inserted 13/16 in..

(Refer to figure 6)

1.

Independent base (four corner type)

2.

Independent base (with center support type)

3.

Beam base (Horizontal)

4.

Beam base (Vertical)

5.

Center of the product

(Refer to figure 7)

1.

Foundation bolt point (

φ

9/16 in. dia, : 4positions)

2.

(Depth of product)

3.

(Inner dimension of the base)

4.

(Outer dimension of the base)

NOTE

There are restrictions on the refrigerant pipe connecting order 
between outside unit in the case of the multi system.
See “

2-1 Combination

” for detail.

When installing on a roof, make sure the roof floor is strong enough 
and be sure to water-proof all work.

Make sure the area around the machine drains properly by setting up 
drainage grooves around the foundation.
Drain water is sometimes discharged from the outside unit when it is 
running.

For anti-corrosion type, use nuts with resin washers. If the paint on 
nut connections comes off, the anti-corrosion effect may decrease.

h2

59

<Front side>

<Suction side>

19 - 5/8 +

h2

2

or more

Service

space

h1

2

or more

h1

19-5/8

+

Model

A (in.)

B (in.)

72 · 96 · 108PA type

48-13/16

43-3/8

13/16 in.

Resin washers

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: