background image

English

18

6.

After completing the additional refrigerant charging, record the charging 
amount on the accessory “REQUEST FOR THE INDICATON” label 
(Installation records) and adhere it to the back side of the front panel.

11-2-2 Procedure of check operation

Check operation perform the following work. Do the check operation 
following below.
Otherwise, malfunction code “U3” will be displayed in the remote 
controller and nomal operation can not be carried out.

„

Check of shutoff valve opening

„

Check of miswiring

„

Judgment of piping length

„

Check of refrigerant overcharge

NOTE

Check operation can not carried out at outdoor temp. less than 23°F.
Perform the check operation at day or time that outdoor temp. is 23°F 
or more.

[Check Operation Procedure]

(1) Close the EL. COMPO. BOX lid and all front panels except as the 

side of the EL. COMPO. BOX and turn on the power to the outside 
unit and all connected indoor units. (Be sure to turn the power on at 
least 6 hours before operation in order to have power running to the 
crank case heater.)

(2) Make the onsite settings as needed using the push button (BS1-

BS5) on the outside unit PC-board (A1P) with the power on. (See 

“12 Onsite Settings”

)

(3) Perform the check operation following the Check Operation Method 

of the [Service Precautions] label (lower) on the EL. COMPO. BOX 
lid. (See figure 32) The system operation for about 40~60 minutes 
and automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after 
the system stop, check operation is completed. Normal operation will 
be possible after 5 minutes. If the malfunction code is displayed in the 
remote controller, correct the malfunction following [Remote control-
ler displays malfunction code] and perform the check operation again.

(Refer to figure 32)

1.

EL. COMPO.BOX (1) lid

2.

(Only RXYQ~PAYD
EL. COMPO.BOX (2) lid

3.

[Service Precaution] label (upper)

4.

[Service Precaution] label (lower)

NOTE

For interrupting the check operation, push RETURN button (BS3).

[Remote controller displays malfunction code]

NOTE

If any malfunction codes other than the above are displayed, check the 
service manual for how to respond.

12. ONSITE SETTINGS

NOTE

In the case of a multi system, all onsite settings should be made on the 
master unit. Settings made on sub units are invalid.
The outside unit to which the indoor unit transmission wire are con-
nected is the master unit, and all other units are sub units.

Use the push button switches (BS1 through BS5) on the outside unit 
PC-board (A1P) to make the necessary onsite settings.
See the “Service Precautions” label (upper) on the EL. CONPO. BOX lid 
for details on the positions and operating method of the push button 
switches and on the onsite setting.
Make sure to record the setting on the accessory “REQUEST FOR THE 
INDICATION” label.

WARNING

Electric Shock Warning

Use an insulated rod to operate the push buttons via the inspection door 
of EL. COMPO. BOX lid. 
There is a risk of electric shock if you touch any live parts, since this 
operation must be performed with the power on.

13. TEST RUN

13-1 Before test run

Make sure the following works are completed in accordance with the 
installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Additional refrigerant charge

„

Check operation

Check that all work for the indoor unit are finished and there are no 
danger to operate.

13-2 Test Run

After all works are completed, operate the unit normally and check the 
following.
(1) Make sure the indoor and outside units are operating normally.
(2) Operate each indoor unit one by one and make sure the correspond-

ing outside unit is also operating.

(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller 

to see if they operate properly.

NOTE

Heating is not possible if the outdoor temperature is 75°F or higher. 
Refer to the Operation manual.

If a knocking sound can be heard in the liquid compression of the com-
pressor, stop the unit immediately and then energize the crank case 
heater for a sufficient length of time before restarting the operation.

Once stopping, the compressor will not restart in about 5 minutes 
even if the On/Off button of the remote controller is pushed.

When the system operation is stopped by the remote controller, the out-
side units may continue operating for further 5 minutes at maximum.

The outside unit fan may rotate at low speeds if the Night-time low 
noise setting or the External low noise level setting is made, but this 
is not a malfunction.

If the check operation was not performed at first istallation, the malfunc-
tion code “U3” will be displayed in the remote controller. Perform the 
check operation following 

“11-2-2 Procedure of Check Operation”

.

Malfunc-
tion code

Installation error

Remedial action

E3, E4
F3, F6
UF

The shutoff valve of the outside 
unit is left closed.

Open the shutoff valve.

U1

The phases of the power to 
the outside unit is reversed.

Exchange two of the three phases (L1, 
L2, L3) to make a proper connection.

U1
U4
LC

No power is supplied to an 
outside or indoor unit (includ-
ing phase interruption).

Make sure the power source wire is 
properly connected to the outside or 
indoor unit and revise if necessary.

UF

There is conflict on the con-
nection of transmission wir-
ing in the system.

Check if the refrigerant piping line and 
the transmission wiring are consistent 
with each other.

E3
F6
UF

Refrigerant overcharge.

Recalculate the additional amount refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

E4
F3

Insufficient refrigerant.

Check if the additional refrigerant 
charge has been finished correctly.

Recalculate the additional amount 
refrigerant from the piping length and 
add the adequate amount.

U7, U4
UF, UH

Field wiring is connected to "TO 
MULTI UNIT (Q1,Q2)" terminal 
on the outside unit PC-board 
(A1P) when the system is one 
outdoor system.

Remove the line from the “TO MULTI UNIT 
(Q1, Q2)” terminal.

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: