background image

English

2

• Make sure that all wiring is secured, that specified wires are 

used, and that no external forces act on the terminal connec-
tions or wires. Improper connections or installation may re-
sult in fire.

• When wiring, position the wires so that the terminal box lid can be 

securely fastened. Improper positioning of the terminal box lid 
may result in electric shocks, fire, or the terminals overheating.

• Before touching electrical parts, turn off the unit.

• Be sure to install a ground fault circuit interrupter if one is not 

already available. This helps prevent electrical shocks or fire.

• Securely fasten the outside unit terminal cover (panel). If the 

terminal cover/panel is not installed properly, dust or water 
may enter the outside unit causing fire or electric shock.

• When installing or relocating the system, keep the refrigerant 

circuit free from substances other than the specified refriger-
ant (R-410A) such as air. Any presence of air or other foreign 
substance in the refrigerant circuit can cause an abnormal 
pressure rise or rupture, resulting in injury.

• Do not change the setting of the protection devices. If the 

pressure switch, thermal switch, or other protection device is 
shorted and operated forcibly, or parts other than those spec-
ified by Daikin are used, fire or explosion may occur.

CAUTION

• Do not touch the switch with wet fingers. Touching a switch with 

wet fingers can cause electric shock.

• Do not allow children to play on or around the unit to prevent 

injury.

• Do not touch the refrigerant pipes during and immediately af-

ter operation as the refrigerant pipes may be hot or cold, de-
pending on the condition of the refrigerant flowing through 
the refrigerant piping, compressor, and other refrigerant cycle 
parts. Your hands may suffer burns or frostbite if you touch 
the refrigerant pipes. To avoid injury, give the pipes time to re-
turn to normal temperature or, if you must touch them, be sure 
to wear proper gloves.

• Heat exchanger fins are sharp enough to cut.

To avoid injury wear glove or cover the fins when working
around them.

• Install drain piping to proper drainage. Improper drain piping 

may result in water leakage and property damage.

• Insulate piping to prevent condensation.

• Be careful when transporting the product.

• Do not turn off the power immediately after stopping opera-

tion. Always wait for at least 5 minutes before turning off the 
power. Otherwise, water leakage may occur.

• Do not use a charging cylinder. Using a charging cylinder may 

cause the refrigerant to deteriorate.

• Refrigerant R-410A in the system must be kept clean, dry, and 

tight.

(a) Clean and Dry -- Foreign materials (including mineral oils 

such as SUNISO oil or moisture) should be prevented from 
getting into the system.

(b) Tight -- R-410A does not contain any chlorine, does not 

destroy the ozone layer, and does not reduce the earth’s pro-
tection again harmful ultraviolet radiation. R-410A can con-
tribute to the greenhouse effect if it is released. Therefore 
take proper measures to check for the tightness of the refrig-
erant piping installation. Read the chapter Refrigerant Pip-
ing and follow the procedures.

• Since R-410A is a blend, the required additional refrigerant 

must be charged in its liquid state. If the refrigerant is charged 
in a state of gas, its composition can change and the system 
will not work properly.

• The indoor unit is for R-410A. See the catalog for indoor mod-

els that can be connected. Normal operation is not possible 
when connected to other units.

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types). Install the indoor unit far 
away from fluorescent lamps as much as possible.

• Indoor units are for indoor installation only. Outdoor units can 

be installed either outdoors or indoors. 

• Do not install the air conditioner in the following locations:

(a) Where a mineral oil mist or oil spray or vapor is produced, for 

example, in a kitchen.
Plastic parts may deteriorate and fall off or result in water 
leakage.

(b) Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c) Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the 
control system and cause the unit to malfunction.

(d) Where flammable gas may leak, where there is carbon fiber, 

or ignitable dust suspension in the air, or where volatile 
flammables such as thinner or gasoline are handled. Operat-
ing the unit in such conditions can cause a fire.

• Take adequate measures to prevent the outside unit from being 

used as a shelter by small animals. Small animals making con-
tact with electrical parts can cause malfunctions, smoke, or 
fire. Instruct the customer to keep the area around the unit 
clean.

NOTE

• Install the power supply and control wires for the indoor and out-

door units at least 3.5 feet away from televisions or radios to pre-
vent image interference or noise. Depending on the radio waves, 
a distance of 3.5 feet may not be sufficient to eliminate the noise.

• Dismantling the unit, treatment of the refrigerant, oil and addi-

tional parts must be done in accordance with the relevant lo-
cal, state, and national regulations.

• Do not use the following tools that are used with conventional 

refrigerants: gauge manifold, charge hose, gas leak detector, 
reverse flow check valve, refrigerant charge base, vacuum 
gauge, or refrigerant recovery equipment.

• If the conventional refrigerant and refrigerator oil are mixed in 

R-410A, the refrigerant may deteriorate.

• This air conditioner is an appliance that should not be acces-

sible to the general public.

• The wall thickness of field-installed pipes should be selected 

in accordance with the relevant local, state, and national reg-
ulations.

1-2 Special notice of product

[CLASSIFICATION]

This air conditioner comes under the term “appliances not accessible to 
the general public”.

[REFRIGERANT]
 VRV

III

 System use R410A refrigerant.

The refrigerant R410A requires strict cautions for keeping the sys-
tem clean, dry and tight.
Read the chapter “REFRIGERANT PIPING” carefully and follow 
these procedures correctly.
A. Clean and dry

Foreign materials (including mineral oils such as SUNISO oil or 
moisture) should be prevented from getting mixed into the system.

B. Tight

Take care to keep the system tight when installing.
R410A does not contain any chlorine, does not destroy the ozone 
layer, and does not reduce the earth’s protection against harmful 
ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is 
released.

Since R410A is a mixed refrigerant, the required additional refrigerant 
must be charged in its liquid state. If the refrigerant is charged in a state 
of gas, its composition changes and the system will not work properly.

[DESIGN PRESSURE]

Since design pressure is 478 psi, the wall thickness of pipes should be 
more carefully selected in accordance with the relevant local and 
national regulations.

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: